Product Description

These instructions describe the installation

procedure for the wire connector accessories on

Record Plus™

FE-frame circuit breakers. The wire

connector kits are available in five variants:

Product Catalog

Numbers

Wire Range

FCAL15/ FCALK15

#14-6/0 AWG Al

#4-3/0 AWG

FCALK15LV Control

Wire Terminal Kit

Use 250-series fully insulated

receptacle connectors

(ANSI/NEMA. DC-2-1982)

FCAL16/FCALK16

#8-1 AWG

#1/0-350Kcm

Table 1. List of accessory lug kits.

The FCALK15/FCALK16 kit is suitable for two and
three-pole applications. The FCALK15/FCALK16
kits contain 3 lug wire connectors, a lug cover, and 3
front covers. The FCAL15/FCAL16 catalog number
is a replacement lug kit that contains 1 lug wire
connector and 1 front cover for replacement use.
The FCALK15LV/FCALK16LV kits provide control
wire terminations at the lug.

Step 1 – Unpack and Inspect

Unpack the wire connector kit and inspect the parts

for any shipping damage. Verify that all parts are

supplied, as listed in Table 2 and illustrated in

Figures 1 and 2. Numbers in brackets in the text and

the figures refer to the item numbers in Table 2.

Item Description

FCAL15

FCALK

15

FCALK

15LV

FCAL16

FCALK

16

FCALK

16LV

1 Lug

Cover

1

1

1

1

2

Lug (Wire Connector)

1

3

3

1

3

3

3

Front

Cover

1 3 1 3

4

Control Wire Terminal

3

3

5

Control Wire Front

Cover

3 3

6

Adhesive Base Cover

1

1

1

1

1

1

Table 2. List of parts in the lug accessory kits.

Step 2 – Installation



1. Please review installation instructions fully

before installing lug kit. Lug kit installation
is best done before breaker is mounted.
Installation of front cover [3] (described
below) may best be done before or after
mounting, depending on application.

2. Align lug cover [1] terminal openings with

breaker terminations. Push lug cover
assembly over breaker terminations until lug
cover is seated fully in, as illustrated in Figure
2. Be sure lug [2] is pushed and fully seated
into lug cover [1]. Hex drive of lug screw, lug
cover top hole, and IP20 hole on front face of
breaker should be aligned to allow for hex
driver access to lug screw.

3. Peel off the cover on the Adhesive Base Cover

[6] and affix on the lug cover and breaker
interface on line and load sides as illustrated
in Figure 3.

4. Use joint compound recommended by the

wire manufacturer when using aluminum

wire.

5. Front Cover Installation [3] (Please refer to
Figure 2):

a. FCAL15/FCALK15/FCALK16/FCAL16

Front Cover Installation: Install front covers

[3] by inserting tab into square slot in lug

cover [1] and pushing front cover [3] to seat

on lug cover [1]. This is intended to be a

press fit. Apply pressure to front cover [3] so

that it fully sits on the lug cover [1].

b. FCALK15LV/FCALK16LV Control Wire

Terminal Kit: Place the control wire terminal

[4] on the breaker terminal strap with the lug

[2] installed. Install control wire front covers

[5] by inserting tab into lug cover [1],

guiding the control wire terminal tab [4]

through opening in the front cover [5], and

pushing front cover [5] into press fit on lug

cover [1]. USE ONLY 250-SERIES FULLY

INSULATED UL LISTED RECEPTACLE

CONNECTORS. 90° flag-style connectors are

recommended.

Note: When using aluminum wire, use of a joint

compound recommended by the wire
manufacturer.
Important: Dans les cas d'emploi de cable
aluminum, utilizez le lubricant recommende b

y

par le fabricant.

Advertising