GE Industrial Solutions Record Plus Wire Connector Lug Kits: FE250 User Manual
Page 3
Advertising
[1]
Figure 2. Installation of lug kit components on FE breaker.
6. Strip 20.2 - 23.4 mm (13/16 - 15/16 in)
insulation from end of wire.
7. Install wire and torque lug screw with 6mm
hex wrench for FCAL15 and FCALK15. 8mm
driver is used for FCAL16 and FCALK16
according to Table 3. Check to make sure all
terminals are torqued to the proper value. (1
N-m = 8.84 lb-in)
[1]
[5]
[4]
[3]
[2]
Available
only in
LV Kit
[2]
[6]