DEH40324 Installation Instructions

g

Record Plus™

Molded Case Circuit Breaker

Accessories

Auxiliary and Bell Alarm Switches

Congratulations and thank you for choosing the
Record Plus™

family of current-limiting circuit

breakers. These UL-listed auxiliary and bell alarm

switches are suitable for use with the FB100, FC100,

FE150, FE250, FG400, and FG600 circuit breaker

series.

Record Plus™

circuit breakers are designed with a

full line of integrated accessories. All units use the

latest in integrated modular circuit breaker

technology for flexibility in application and

maximizing the product’s utilization and

capabilities.
Record Plus™

circuit breakers are all listed by

Underwriters Laboratories to the UL489 standard

and may be listed to CSA Standard C22.2, No. 5

and IEC60947-2.

They can also be used with our molded case

switches, which are listed per Underwriters

Laboratories to the UL489 standard.

Record Plus™

circuit breakers and their accessories

are designed and manufactured to exceed our

global customers’ high standards for reliability and

quality.

WARNING

: DANGER of electrical shock or injury.

Ensure that ALL electrical power supplies are OFF

before installing or removing any devices. The

breaker, trip unit, or accessories MUST ONLY be

installed and serviced by QUALIFIED personnel. See

NEMA publication AB4.
AVERTISSEMENT: Danger contre les risques

d'électrocutions. S'assurer avant TOUTES

manipulations du disjoncteur que les différentes

sources d'alimentation sont en position OFF. Les

disjoncteurs, unités de protection, ou accessoires

doivent être installés par des personnes qualifiées et

habilitées. Lira NEMA publication AB4.

Figure 1. Bell alarm and auxiliary switches.

CAUTION: This product is NOT suitable for use in

equipment not specifically design to accept it.

Contact the equipment manufacturer for possible

equipment modifications.
ATTENTION: Cet appareil nedoit pas etre employe

dans un equipement non specialement adapte a cet

effet. Contactez le constructeur concernant les

possibles modifications a apporter a l'equipement.

Product Description

The auxiliary and bell alarm switches covered by these

instructions are illustrated in Figure 1. A key for the

different symbols used in these instructions is found in

Table 1. Catalog numbers for the various switch

configurations are listed in Table 2.
Note that contact position for the auxiliary switch is

shown with the breaker in the open position. Bell alarm

contact position is shown with the breaker in the

untripped position.
Mechanical-trip bell alarms are activated by the trip unit

(overcurrent or short circuit), undervoltage release,

shunt trip, or push-to-trip button. Overcurrent/short-

circuit trip bell alarms are activated by the trip unit only

and are not available for FB and FC breakers.

Symbol Description

Right-hand pocket auxiliary switch

Left-hand pocket auxiliary switch

Mechanical-trip bell alarm (all tripping

functions)

Overcurrent / short-circuit trip bell alarm

(not available on FC breakers)

Table 1. Key to symbols.