Bell Alarm Switches

Auxiliary Switches

Switch Symbols

IEC UL/CSA

FABAM10 FABAT10 FAS10L FAS10R

Form A

FABAM01 FABAT01 FAS01L FAS01R

Form B

FABAM11 FABAT11 FAS11L FAS11R

Form C

Table 2. Catalog numbers for Record Plus™ auxiliary and bell alarm switches.

Step 1 – Unpack and Inspect

Unpack the bell alarm or auxiliary switch kit and inspect

it for shipping damage. Read the circuit breaker

installation instructions carefully. Insure that the circuit

breaker and the accessory have the proper ratings for

current, voltage, interruption, and contact duty; wire

routing; installation; and operation for the application.
Form C switches are factory installed with #18 AWG

wires, 36 inches long. All other switches with the catalog

number suffix W are factory installed with #16 AWG

wire, 36 inches long.
Wire colors for each switch catalog number are listed in

Table 3. Contact ratings for Form C switches are listed

in Table 4. Contact ratings for Form A and B switches

are listed in Table 5.

Cat. No.

Commo

n

1

NC

2 4

NO

4

FAS01L White Brown/White

FAS10L

White

Red

FAS11L White Brown/White Red

FAS01R White Brown/White

FAS10R

White

Red

FAS11R White Brown/White Red

FABAT01 Orange

Pink

FABAT10

Orange

Grey

FABAT11 Orange

Pink

Grey

FABAM01 Yellow

Purple

FABAM10

Yellow

Brown

FABAM11 Yellow

Purple

Brown

Table 3. Wire colors for auxiliary and bell alarm switches.

Vac A Vdc A

Low-energy gold-plated contacts,

catalog number suffix G

5 1 5 1

12 1 12 1
24 1 24 1
30 1 30 1

Standard contacts

48 5 48

0.3

60 5 60 0.3

120 5 110 0.3
220 5 125 0.3
240 5
277 5

Table 4. Contact ratings for Form C switches; cat. nos. FA/FEBAT11,

FABAM11, FAS11L, FAS11R.

Vac A Vdc A

A600/AC15 Q300/DC13

12 10* 12 2.5
24 10* 24 2.5
48 10* 48 1.1
60 10* 60 1

110 6* 110 0.55
120 6* 125 0.55
220 3 220

0.27

240 3 250

0.27

380

1.9 (2.0

for AC15)

300

0.2 for

DC13

480 1.5

500

1.4 (1.5

for AC15)

600 1.2

Maximum VA:

Making – 7200 VA

Breaking – 720 VA

Maximum VA = 69 VA

Maximum Thermal

Current = 10 A

* 5 A for screw-type

terminals

Maximum Thermal

Current = 69 VA

Minimum low-energy switching: IEC609747-5-4

12 5

mA 12 5

mA

Table 5. Contact ratings for Form A and B switches; cat. nos.

FA/FEBAT10/01, FABAM10/01, FAS10L/01L, FAS10R/01R.

Step 2 – Breaker Status

Either trip the circuit breaker by activating the red trip

button on the front of the breaker or move the breaker

handle to the

OFF

position, both shown in Figure 2.

(a)

(b)

Figure 2. (a) Tripping the breaker or (b) turning it OFF.