GE Industrial Solutions A-Series II Panelboards SG User Manual

A-series, Ii panelboards

Advertising
background image

DEH40150

DEH40150 Rev.No.03

1

g

A-Series

®

II Panelboards

AD/AE/AQ Type P & N Power Panel
SG Three-Phase Circuit Breaker Kits

Introduction
These instructions describe the installation of SG three-phase circuit breaker kit into an
A-Series

®

II panelboard. These kits are for use in panelboards ordered with Un-Specified

Space.
The catalog number for three-pole kit is ASPP6SG3S

Part List for ASPP6SG3S

Table 1.

ITEM #

DESCRIPTION

PART #

QTY

1

STRAP FOR B PHASE

315A7046P8

1

2

STRAP FOR A PHASE

315A7046P7

1

3

STRAP FOR C PHASE

315A7046P9

1

4 (SPOOL)

315A7036P22

3

5 (SCREW-SPOOL)

315A7037P5

3

6 (WASHER-SPOOL)

75A105503P111 3

7 (SCREW-BUS)

315A7034P7

3

8 3P

BRACKET

139C5500P83

1

9

SCREW, BKT TO RAIL

N667P16008B6

2

10

XMAS TREE

315A7077P1

3

11

FILLER PLATE, SG/TFG

139C5503P103

1

12

SCREWS , #10-32 X 3/8

N722P16006B6

4

13 BRACKET

INSULATION

10086929P11

1

14 INSULATOR

B

10086929P5

1

15 INSULATOR

A

10086929P7

1

16 INSULATOR

C

10086929P6

1

17 BREAKER

MOUNTING

SCREWS

N37P16060B6 2

19

SPRING LOCK WASHER #12

N405P40B6

2

Installation

WARNING: Before attempting to install one of these kits, remove all power from the
panelboard.
Use the following procedure to install a SG circuit breaker kit. Call-out numbers in the
illustrations and numbers in brackets in the text refer to the Item Numbers in Table 1.
Installation of a three-pole kit is illustrated in Fig.no.1 or Fig.no.2.

1. Remove the interior assembly from its packaging and verify that all parts are

present, as given in the parts list.

2. Remove the 8 screws (600A and 800A panels) securing the dead front to

panelboard interior. Lift off the dead front and place it and the screws aside.

3. Remove the circuit breaker kit from its packaging and verify that all parts are

present, as given in the packing list.

Advertising