Figure 3. Removing the shield inserts from the shield for SG breaker installation in
A -Series

®

II panelboard.


14. To install branch breaker (kit ASPP6SG3S), place the new filler plate [11] over

the dead front so that the four same-size holes line up with the threaded holes of
the dead front, as illustrated in Fig.no.4. Fasten filler plate to the dead front with
four #10-32 x

3

/

8

screws [12] tightened to 27-36 lb-in.

15. Reattach the dead front to the interior with the 8 screws removed in step 2.

Tighten the screws to 27-36 lb-in.

16. If SG breaker has to be installed immediate after cross bar as shown in Figure 5

then gap between the breaker and crossbar has to be 0.002 inch.