Installation Instructions

Pro-Stock Panelboards with TRANQUELL

Medium Exposure TVSS

2020000903 (10/04) Page 2 of 9

X3

X2

X1

X0

PHASE C

PHASE B

PHASE A

NEUTRAL

Bonding Jumper
Ref. NEC 250-30 (a) (1)

Grounding Electrode
Ref. NEC 250-30 (a) (4)

Primary Dist.

Panel w/Overcurrent

or Service Disconnect

Means

Grounding Electrode
Conductor Ref. NEC
250.62 - 250.64 - 250.66

GROUND

Equipment Grounding
Conductor Ref. NEC
250.32 (B) (1)

N

G

Note:
Primary transformer windings
not shown for simplicity

NEC Grounding arrangement for a separately derived system in which the

grounding electrode conductor connection is made at the transformer

X3

X2

X1

X0

PHASE C

PHASE B

PHASE A

NEUTRAL

Bonding Jumper
Ref. NEC 250-30 (a) (1)

Grounding Electrode
Ref. NEC 250-30 (a) (4)

Primary Dist.

Panel w/Overcurrent

or Service Disconnect

Means

Grounding Electrode
Conductor Ref. NEC
250.62 - 250.64 - 250.66

Equipment Grounding
Conductor Ref. NEC
250.32 (B) (1)

N

G

NEC Grounding arrangement for a separately derived system in which the

grounding electrode conductor connection is made at the first disconnecting means

Note:
Primary transformer windings
not shown for simplicity