A – Unpack and Inspect


Unpack the breaker and inspect it for any shipping damage.
Ensure that the breaker has the proper current, voltage, and
interrupting ratings for the application. Also check breaker
operation, as described in section D. Install any internal
accessories, as described in section B, and terminal lugs, as
described in section C, using the supplied installation
instructions. Check all accessories for proper voltage ratings,
installation, wiring routing, and operation. If internal
accessories have been installed, attach the appropriate labels
to the side of the breaker. An example of these labels is
illustrated in Figure 1.B.

FASHTJ

C1 Black

C2 Black

110/130V 50/60Hz
110/125V DC

Inrush 40mA

B – Installation

Internal Accessories

Install any internal accessories, following the instructions
supplied with each accessory. The available accessories and
their mounting locations are listed in Table 1,Table 2,Table 3


and Table 4. Check all accessories for proper installation and
wire routing. Verify breaker operation with the installed
accessories.

Internal Accessory

Normally

Open

Normally

Closed

Max. No. Of

Accessories

Auxiliary switch left

mounted

FAS10LW FAS01LW

3

Auxiliary switch right

mounted

FAS10RW FAS01RW

2

Bell alarm mechanism

FABAM10W

FABAM01W

1

Bell alarm trip unit

FABAT10W FABAT01W

1

Table 1. Auxiliary switch and bell alarm accessories.

Trip Voltage

Shunt Trip

Under voltage

Max. No. Of

Accessories

12 Vdc

FASHTBW

1 ST

24 Vac/Vdc

FASHTDW

FAURDW

1 ST or UV

48 Vac/Vdc

FASHTFW

FAUVRFW

1 ST or UV

110–130 Vac
110–125 Vdc

FASHTJW

FAUVRJW

1 ST or UV

120 Vac

FASHTKW

1 ST

220/240 Vac

250 Vdc

FASHTNW

FAUVRNW

1 ST or UV

277 Vac

FASHT7W

FAUVR7W

1 ST or UV

400/480 Vac

FASHTUW

FAUVRUW

1 ST or UV

Table 2. Shunt trip and under voltage accessories.

Accessory/Kit

Catalog #

Rating (Voltage)

Description

FAMBAT

240 / 480 / 600

Spare Battery Module

FAMGFT2

240 / 480 / 600

Ground Fault Trip + Fault

Type Indicators

FAMGFM2

240 / 480 / 600

Ground Fault Trip +

Modbus

Communications

FAMFGS2

240 / 480 / 600

Ground Fault Trip + 2-

Channel Load Shedding

FAMAM2

240 / 480 / 600

Ammeter with 4-digit

LCD Display

FAMB2

240 / 480 / 600

Spare Filler Module

FAMGAT2

240 / 480 / 600

Ground Fault Alarm +

Fault Type Indicators

FAMGAM2

240 / 480 / 600

Ground Fault Alarm +

Modbus

Communications

FAMGAS2

240 / 480 / 600

Ground Fault Alarm + 2-

Channel Load Shedding

FAMSM2

240 / 480 / 600

2-Channel Load

Shedding + Modbus

Communications

FAMST2

240 / 480 / 600

2-Channel Load

Shedding + Fault Type

Indicators

FAMMT2

240 / 480 / 600

Fault Type Indicators +

Modbus

Communications

FAMECM

240 / 480 / 600

External

Communications and

Contact Module

Table 3: Module Accessories/Kits for SMR2 (Internal Accessories).

Figure 1.A. Installation of typical breaker accessories. See the
Buylog® for details.

Figure 1.B. Accessory label.