I-T-E 1600 Ampere Red Frame Breakers Only

1. Attach the mounting brackets removed from the old

copper terminals in Section 3, step 6 of I-T-E 1600
Ampere Breakers, onto the insulated housings, using
the Philips-head screws removed in step 5, as shown
in Figure 16.

2. Attach a new copper load-terminal extension to each

insulated housing with the two

3

/

8

-16 x 1" bolts, lock

washers, and flat washers provided, as shown in
Figure 16.

3. Insert the two #10-32 x 1

1

/

4

" screws, with the lock

washers, flat washers, and nuts provided, through
the insulated housing, as shown in Figure 16.

4. Assemble a copper CT post, CT, and insulating

barrier onto each insulated housing. Insert and finger
tighten the

1

/

2

-13 x 1

1

/

2

" bolt, with lock and flat

washers, into each CT post, as shown in Figure 17.

Figure 16. Terminal assembly for K-1600 red frame

breaker.

Figure 17. CT assembly for K-1600 red frame breaker.