Mounting the Trip Unit Bracket

1. Rotate the breaker to the upright position. Remove

and save the Philips-head screws and washers at the
front of the top cover, as shown in Figure 26.

16

2. Attach the insulating barrier to the mounting bracket

with the wire ties provided, as shown in Figure 27.

3. Attach the trip unit bracket and shield assembly to

the top cover with the screws and washers removed
in step 1, as shown in Figure 28. Be sure that the
insulating barrier is between the arc chutes and the
bracket.

Figure 26. Removing the top cover screws.

Insulating

Barrier

Bracket

Figure 27. Trip unit bracket and insulating barrier

assembly.

Figure 28. Trip unit bracket attached to the breaker.