GE Industrial Solutions ProTrip Conversion Kits LA-600, LA-800, and LA-1600 User Manual

Page 14

Advertising
background image

14

3. Verify that the wiring harness connections to the

sensors have the proper polarity (white lead to
common, black lead to tap), as shown in the
cabling diagram in Figure 14.

4. On ground fault breakers serving four-wire

loads, check that the neutral sensor is properly
con nected, as indicated in Figure 14. In particu-
lar, check the following:

a. Verify that the neutral sensor has the same

rat ing and tap setting as the phase sensors.

b. Verify continuity between the neutral sensor

and its equipment-mounted secondary
disconnect block. Also check for continuity
from the breaker-mounted neutral secondary
disconnect block through to the trip unit
wiring harness connector.

c. If the breaker’s lower studs connect to the

power source, then the neutral sensor must
have its load end connected to the source.

d. Verify that the neutral conductor is carrying

only the neutral current associated with the
breaker’s load current (the neutral is not
shared with other loads).

5. If the preceding steps fail to identify the prob-

lem, then measure the sensor resistances. The
appro priate values are listed in Tabl e 1. Since
the phase and neutral sensors are electrically
identical, their resistances should agree closely.

Breaker

CT Rating, A

Resistance, ohms

LA-600

150
225
600

10.1–15.2

14.5–22

4–58

LA-800

150
400
800

10.1–15.2

27–41
51–77

LA-1600

800

1600

54–81

110–166

Table 1. CT resistance values.

Advertising