Installing and Adjusting the Flux Shifter
Assembly

Use the following procedures to install and adjust
the new flux shifter assembly, shown in Figure 4.
Numbers in brackets in the text refer to the num-
bered parts in Figure 4. The breaker should still be
resting on its back from the previous procedure
(removing the old components).

Installing the Flux Shifter Assembly

Figures 6 and 7 show two views of the completed
flux shifter installation.

1. Check that the diameters of the two flux shifter

mounting holes, shown in Figure 5, are .30 inch.
If they are less than this size, drill them out to
.30 inch (use an N bit).

2. Loosen the screw on the flux shifter reset link [2]

and move the link to the bottom of its slot.

3. Remove and save the nut, lock washer, and flat

washer from the two mounting studs [6] on the
mounting surface of the flux shifter assembly.
Leave the spacers in place, as they are necessary
to ensure proper alignment with the breaker
reset link [7].

4. Install the flux shifter assembly on the right side

of the breaker frame where the original flux
shifter (if present) was removed. The two
mounting studs should fit through the existing
(or modified) holes in the frame, as shown in
Figure 5. Secure the flux shifter assembly to the
frame with the flat washer, lock washer, and nut
removed in step 3.

Flux Shifter Adjustment

1. With the breaker in the open (reset) position,

depress the flux shifter reset arm [1] so that
dimension A is held at about 0.4 inch.

2. Move the flux shifter reset link [2] up to contact

the breaker reset link [7] and take up any travel
in the breaker link.

3. Tighten the screw on the flux shifter reset link

[2] to secure it in position. The flux shifter is
now in its reset position.

4. Check that there is clearance between the reset

pin [5] and the reset latch [4] with the breaker in
the OPEN (reset) position. When the breaker is
CLOSED, the flat of the reset pin [5] must rest
against the reset latch [4].

Figure 4. Flux shifter assembly.

Figure 5. Flux shifter mounting area (LA-800 shown).

Breaker

Reset

Link

Trip

Paddle

Mounting

Holes

Advertising