Product description, Step1 - unpack and inspect – GE Industrial Solutions Record Plus TDM, NEMA 4__4X: FC100 User Manual

Page 2

Advertising
background image























Figure 2. Parts supplied with the FC100 THCH45 Operator kits.

[9]

Figure 2c. THCH45 Handle Kit.

Item Description

Qty

1

Screw, #8-32 x 2.81"

4

2

Base-crank assembly (Direct

Mount)

1

3 Grounding

Wire

1

4

Screw, #8-32 x 0.312"

4

5

Base-crank assembly (Door

Mount)

1

6 Coupler

1

7

Screw, #8-32 x 0.312"

4

8 Handle

Arm

1

9

THCH45 Handle Kit

1

Table 1. List of parts in the FC100 THCH45 operator kit.

*Note: Item 9 should be ordered separately.

[5]

[6]

[7]

[8]

[1]

[4]

Figure 2b. FCNRM4.

[1]

[2]

[3]

[4]

Figure 2a. FCNRM2.

Product Description

These instructions describe the installation

procedure for the Rotary Handle THCH45

operator accessory on

Record Plus™

circuit

breakers, as shown in Figures 1a & 1b.
THCH45 operator is available in two variants:
• FCNRM2 provides the necessary parts for

direct mounting of the handle on the

breaker mechanism through the enclosure

door, with a box depth of 5.0 inches (127

mm), as shown in Figure 1a.Maintain the

dimension “H” [4.69 inches (119.18)] as

shown in Figure 9.

• FCNRM4 is for mounting the handle and

operator in enclosures with variable depth,

as shown in Figure 1b. Maintain the

dimension “H” [Min 7.25 inches (184.0

mm) and Max 15.0 inches (381.0 mm)] as

shown in Figure 10.

Step1 - Unpack and Inspect.

Unpack the rotary handle operating
mechanism kit and inspect the parts for any
shipping damage. Verify that all parts are
supplied, as listed in Table 1. The parts are
illustrated in Figure 2.
Note that the numbers in brackets in the

following figures and installation instructions

refer to the item numbers in Table 1.