Data sheet – GE Industrial Solutions QBDW025A0B Barracuda Series User Manual

Page 24

Advertising
background image

GE

Data Sheet

QBDW025A0B Barracuda Series; DC-DC Converter Power Modules

36-75Vdc Input; 12.0Vdc, 25.0A, 300W Output

May 9, 2013

©2012 General Electric Company. All rights reserved.

Page 24

STATUS_WORD [0x79]

Command support: full implementationfor supported functions (note: Fans, MFR_SPECIFIC,Unknown not supported)

Format

8 bit unsigned (bit field)

Bit Position

15

14

13

12

11

10

9

8

Access r r r r r r r r

Function VOUT

I/POUT

INPUT

MFR_SPEC

1

#PWR_

GOOD

FANS

1

OTHER

1

UN

KNOWN

1

Format

8 bit unsigned (bit field)

Bit

Position

7 6 5 4 3 2 1 0

Access r r r r r r r r

Function

BUSY

1

OUTPUT

_OFF

VOUT_OV

_FAULT

IOUT_OC

_FAULT

VIN_UV

_FAULT

TEMP CML

NONE OF

ABOVE

1

(1) Not supported

STATUS_VOUT [0x7A]

Command support: VOUT_OV_FAULT support, all bit reset supported

Format

8 bit unsigned (bit field)

Bit Position

7

6

5

4

3

2

1

0

Access

r/reset(1)

r/ reset

r/ reset

r/ reset

r/ reset

r/ reset

r/ reset

r/ reset

Function

VOUT_OV

_FAULT

VOUT_OV

_WARN

1

VOUT_UV

_WARN

1

VOUT_UV

_FAULT

1

VOUT_

MAX

_WARN

1

TON_

MAX_

FAULT

1

TOFF_

MAX_

WARN

1

VOUT

TRACKING

ERROR

1

(1) Not supported

STATUS_IOUT [0x7B]

Command support: IOUT_OC_FAULT support, all bit reset supported

Format

8 bit unsigned (bit field)

Bit

Position

7 6 5 4 3 2 1 0

Access

r/ reset(1)

r/ reset

r/ reset

r/ reset r/

reset r/

reset

r/ reset

r/ reset

Function

IOUT_OC

_FAULT

IOUT_OC _LV

_FAULT

1

IOUT_OC

_WARN

IOUT_UC

_FAULT

1

Current Share

Fault

1

In Power

Limiting

Mode

1

POUT_OP

_FAULT

1

POUT_OP

_WARN

1

(1) Not supported

STATUS_INPUT [0x7C]

Command support: VIN_OV_FAULT support, all bit reset supported

Format

8 bit unsigned (bit field)

Bit Position

7

6

5

4

3

2

1 0

Access

r/ reset(1)

r/ reset

r/ reset

r/ reset r/

reset r/

reset

r/ reset

r/ reset

Function

VIN_OV

_FAULT

VIN_OV

_WARN

1

VIN_UV

_WARN

1

VIN_UV

_FAULT

Unit Off

(low input

voltage)

IIN_OC

_FAULT

1

IIN_OC

_WARN

1

PIN_OP

_WARN

1

(1) Not supported

STATUS_TEMPERATURE [0x7D]

Command support: OT_WARN, OT_FAULT supported, all bit reset supported

Format

8 bit unsigned (bit field)

Bit

Position

7 6 5 4 3 2 1 0

Access

r/ reset(1)

r/ reset

r/ reset

r/ reset r/

reset r/

reset

r/ reset

r/ reset

Function

OT_ FAULT

OT_ WARN

UT_

WARN

1

UT_

FAULT

1

reserved reserved reserved reserved

(1) Not supported

Advertising