Accessory configuration – GE Industrial Solutions Power Break II Undervoltage Release 480 & 600 Vac User Manual

Page 2

Advertising
background image

Figure 2. Accessory compartment on front of circuit breaker, with

Undervoltage Release slot indicated.

3. Insert the UVR accessory into the proper slot, as

illustrated in Figure 3. The UVR accessory is keyed for
the correct slot in the accessory compartment. If the
accessory cannot be fully seated in the compartment, check
that the compartment position is correct.

Figure 3. Inserting the Undervoltage Release into the accessory

compartment.

4. Tighten the locking screw on the front of the accessory

until it is snug (torque of 9 in-lb.)

CAUTION: Overtightening the locking screw may damage or
distort the case of the accessory.

ATTENTION: Le serrage excessif de la vis de verrouillage
peut déformer le boîtier d’accessoire.

5. If the breaker is equipped with a MicroVersaTrip Plus or

MicroVersaTrip PM Trip Unit, the UVR accessory can be
configured to activate installed Bell Alarm–Alarm Only or
Bell Alarm with Lockout accessories when a UVR trip
occurs, with the procedure described in the Accessory
Configuration section.

6. Mount the supplied step-down transformer near the circuit

breaker.

7. Connect the control wiring for the UVR to the primary

side of the transformer, marked as the H-numbered
terminals. Table 2 lists the correct transformer primary
taps.

Catalog Number/

Control Voltage

Primary

Connections

Secondary

Connections

9T58K0042 / 480 V

H1, H4

X1, X2

9T58K0062 / 600 V

H1, H4

X1, X3

➀ A jumper must be placed from H2 to H3.

Table 2. Primary and secondary connections for step-down

transformers.

8. Connect the secondary side of the transformer, marked as

the X-numbered terminals, to terminals 29 and 30 of the
terminal block on the right side of the breaker. Table 2
lists the correct transformer secondary taps.

WARNING: 480 Vac and 600 Vac Undervoltage Release
accessories must be used with the supplied step-down
transformer.

AVERTISSEMENT: Les modules de déclenchement à manque
de tension 480 Vac et 600 Vac doivent être utilisés avec le
transformateur abaisseur de tension qui est fourni.

9. Test the UVR to ensure proper operation, according to the

procedures below.

10. Reconnect power to the circuit breaker and any other

accessories.

11. Close and lock or seal the door over the accessory

compartment and Trip Unit to prevent unauthorized
changes to Trip Unit settings and to keep contaminants
out of empty accessory slots.

Accessory Configuration

This section only applies if Bell Alarm–Alarm Only or Bell
Alarm with Lockout accessories are installed in the breaker,
along with a MicroVersaTrip Plus or MicroVersaTrip PM Trip
Unit. If the breaker is equipped with a Power+ Trip Unit, the
factory default settings, listed in Table 3, can not be changed.
The UVR accessory can be configured to activate the Bell
Alarm–Alarm Only or Bell Alarm with Lockout accessories if a
UVR trip occurs. The configuration can be changed by removing
the Trip Unit from the breaker, setting the DIP switches on the
rear of the Trip Unit, and reinstalling the Trip Unit. Figure 4
illustrates the Trip Unit read DIP switches and their functions.
Table 3 lists the switch functions and the factory settings for
each.

Figure 4. Accessory switch on the rear of the MicroVersaTrip Plus™ or

MicroVersaTrip PM™ Trip Unit, showing the factory settings (solid

part indicates that the switch is pushed in on that side).