Test procedure – GE Industrial Solutions Power Break II Undervoltage Release 480 & 600 Vac User Manual

Page 3

Advertising
background image

Switch

Factory
Setting

Function

1

Disabled

Shunt trip activates Bell Alarm–Alarm

Only

2

Disabled

UVR trip activates Bell Alarm–Alarm

Only

3

Enabled

Protection trip activates Bell

Alarm–Alarm Only

4

Disabled

Shunt trip activates Bell Alarm with

Lockout

5

Disabled

UVR trip activates Bell Alarm with

Lockout

6

Enabled

Protection trip activates Bell Alarm

with Lockout

Table 3. Accessory switch settings, including factory defaults.

Description of Switch Settings

Following are descriptions of the effects of each accessory switch
when it is enabled:

1. When a Shunt Trip accessory causes the breaker to trip,

the contacts of the Bell Alarm–Alarm Only also change
state. (The factory switch setting is disabled.)

2. When an Undervoltage Release accessory causes the

breaker to trip, the contacts of the Bell Alarm–Alarm Only
also change state. (The factory switch setting is disabled.)

3. When

a

protection

trip

(long-time,

short-time,

instantaneous, ground-fault, or protective-relay) occurs,
the contacts of the Bell Alarm–Alarm Only also change
state. (The factory switch setting is enabled.)

4. When a Shunt Trip accessory causes the breaker to trip,

the contacts of the Bell Alarm with Lockout also change
state. (The factory switch setting is disabled.)

5. When an Undervoltage Release accessory causes the

breaker to trip, the contacts of the Bell Alarm with
Lockout also change state. (The factory switch setting is

disabled.)

6. When

a

protection

trip

(long-time,

short-time,

instantaneous, ground-fault, or protective-relay) occurs,
the contacts of the Bell Alarm with Lockout also change
state. (The factory switch setting is enabled.)

Procedure for Changing Switch Settings

Change the accessory switch settings with the following
procedure:

WARNING: Before beginning this procedure, turn the breaker
OFF, disconnect it from all voltage sources, and discharge the
closing springs.

AVERTISSEMENT: Avant de commencer cette procédure,
mettre le disjoncteur en position OFF, le déconnecter de toute
tension d’alimentation, et désarmer les ressorts de fermeture.

1. Loosen the four #8-32 screws on the breaker trim-plate

assembly and remove the trim plate.

2. Loosen the four #10-32 screws at the corner of the breaker

cover. Remove the cover from the breaker face.

3. Pull the Trip Unit locking lever to the right, then hold the

Trip Unit near the battery cover and lift it straight out of
the breaker.

4. Refer to Figure 4 and Table 3 to determine the switches

to be changed.

5. Push in the appropriate “Enable” or “Disable” side of the

switch.

6. Confirm all switch settings before reinstalling the Trip

Unit in the breaker.

7. Pull the Trip Unit locking lever to the right. While

holding the lever, carefully align the connector on the rear
of the Trip Unit with the connector in the breaker. Press
down on the Trip Unit, while holding it near the battery
cover. When the Trip Unit is fully seated, slide the locking
lever back to the left.

8. Reinstall the breaker top cover and tighten the four #10-

32 screws to 32 in-lb.

9. Replace the trim plate and tighten the four #8-32 screws

to 20 in-lb.

10. Verify that the switch settings are correct by inducing

breaker trips from the UVR and Shunt Trip or Shunt Trip
with Lockout (if present) and checking the responses of
the Bell Alarm–Alarm Only and Bell Alarm with Lockout
accessories.

Test Procedure

Use the following procedure to test the UVR for proper
operation.

1. Open the breaker.
2. Turn off the power to the UVR.
3. Try to manually close the breaker; the breaker should not

close.

4. Apply at least 80% of the rated voltage specified on the

UVR name plate to the UVR control inputs.

5. Try to close the breaker; it should close as normal.
6. If a MicroVersaTrip Plus or MicroVersaTrip PM Trip

Unit is installed, check that the Trip Unit display is active
(powered).

7. With the breaker closed, reduce the UVR control voltage to

35–60% of the rated voltage; the breaker should trip
within 0.5 second.

8. If a Bell Alarm–Alarm Only or Bell Alarm with Lockout is

present, ensure that they activate (or do not activate) as
selected by the MicroVersaTrip Plus or MicroVersaTrip
PM Trip Unit DIP switches.