Data Sheet

PIM400 Series; ATCA Board Power Input Modules

-36 to -75 Vdc; 400W/10A

June 20, 2013

©2013 General Electric Company. All rights reserved.

Page 3

Absolute Maximum Ratings

Stresses in excess of the absolute maximum ratings can cause permanent damage to the device. These are absolute stress ratings
only, functional operation of the device is not implied at these or any other conditions in excess of those given in the operations
sections of the data sheet. Exposure to absolute maximum ratings for extended periods can adversely affect the device reliability.

Parameter

Device

Symbol

Min

Typ

Max

Unit

Input Voltage

Continuous

All

V

I

-0.5

-75

V

dc

Transient (Pulse duration = 1ms, square wave)

All

V

tr

-100

V

dc

Additionally: Transient Input Undervoltage,
Overvoltage and Impulse per ANSI T1.315-2001(R2006)

All

Reverse Polarity Protection

+75V

V

dc

Holdup Capacitor Voltage

Voltage (with respect to -48V_OUT)

All

V

_

HLDP

100

V

dc

Capacitance

All

C_HLDP

3300

F

Temperature

Normal Operating Ambient Temperature
(See Thermal Considerations section)

All

T

A

-40

85

o

C

Storage Temperature

All

T

stg

-55

125

o

C

Isolation Voltage

Input to MGMT_PWR Output Voltage & Alarm

All

2250

Vdc

Input to SHELF_GND Voltage

All

2250

Vdc

Input to LOGIC_GND Voltage

All

2250

Vdc

CAUTION: This power module is not internally fused. Both A & B feeds and their corresponding returns must be
individually fused.

To preserve maximum flexibility, internal fusing is not included. However, to achieve maximum safety and system protection, the
safety agencies require a fast-acting fuse with a maximum rating of 20 Amps and Voltage Rating >/= 75Vdc for the –48AF, -48BF
VRTN_AF & VRTN_BF feeds. Consult Fusing and fault protection Section of PICMG 3.0 ATCA specifications for additional information.
Based on the information provided in this data sheet on inrush current and maximum dc input current, the same type of fuse with a
lower rating can be used. Refer to the fuse manufacturer’s data sheet for further information.