Page 3
Electrical Specifications
(continued)
Parameter
Device
Symbol
Min
Typ
Max
Unit
Output Voltage Set-point
(V
IN
=V
IN,nom
, I
O
=I
O, max
, T
c
=25°C)
All
V
O, set
47.0 48 49.0 V
dc
Output Voltage Set-Point Total Tolerance
(Over all operating input voltage, resistive load, and temperature
conditions until end of life)
All V
O
47.0
49.0
V
dc
Output Regulation
Line (V
IN
=V
IN, min
to V
IN, max
) All
0.1 0.2
%V
o,set
Load (I
O
=I
O, min
to I
O, max
) All
0.1 0.2
%V
o,set
Temperature (T
c
= -40ºC to +100ºC)
All
0.25 0.5 %V
o,set
Output Ripple and Noise on nominal output
(V
IN
=V
IN, nom
and I
O
=I
O, min
to I
O, max
)
RMS (5Hz to 20MHz bandwidth)
All
100 125 mV
rms
Peak-to-Peak (5Hz to 20MHz bandwidth)
All
300
400
mV
pk-pk
External Capacitance (ESR
> 10 mΩ)
1
All
C
O
440 6500
μF
Output Power (V
o
=48V to 57.6V)
All
P
O,max
450 W
Output Current
All
I
o
0 9.4
A
dc
Output Current Limit Inception (Constant current until V
o
<
V
trimMIN
,
duration <4s)
All
I
O, lim
11.0
12.2 A
dc
Output Short Circuit Current (V
O
≤ 0.25V
dc
) All
I
O, sc
15
A
rms
Efficiency
V
IN
=V
IN, nom
, T
c
=25°C I
O
=I
O, max ,
V
O
= V
O,set
All
η 93.5
94.0
%
Switching Frequency
f
sw
180
kHz
Dynamic Load Response
(Io/t=1A/10s; V
in
=V
in
,nom; T
c
=25°C; Tested with a 470 μF
aluminum and a 10 µF ceramic capacitor across the load.)
Load Change from Io= 50% to 75% of Io,max:
Peak Deviation
Settling Time (Vo<10% peak deviation)
All
V
pk
t
s
2
1.5
%V
O, set
ms
Load Change from Io= 25% to 50% of Io,max:
Peak Deviation
Settling Time (Vo<10% peak deviation)
V
pk
t
s
2
1.5
%V
O, set
ms
1
Note: use a minimum 2 x 220uF output capacitor. Recommended capacitor is Nichicon CD series, 220uF/35V. If the ambient temperature is less
than -20
O
C, use more than 3 of recommended minimum capacitors. When starting into maximum external capacitor, do not simultaneously apply
a Constant Current electronic load set to greater than 0.5 x I
oMAX;
or delay application of full CC load until V
o
>1.0V.
Isolation Specifications
Parameter
Symbol
Min
Typ
Max
Unit
Isolation Capacitance
C
iso
15
nF
Isolation Resistance
R
iso
10
MΩ
General Specifications
Parameter
Device
Symbol
Min
Typ
Max
Unit
Calculated Reliability based upon Telcordia SR-332 Issue 3:
Method
I
Case 3 (I
O
=80%I
O, max
, T
A
=40°C, airflow = 200 lfm, 90%
confidence)
All
FIT 136.3
10
9
/Hours
MTBF 7,338,052
Hours
Weight All
76.4
g
2.69 oz.