Data sheet, Feature specifications – GE Industrial Solutions JRW450U Orca Series User Manual
Page 4
GE
Data Sheet
JRCW450U Orca Series; DC-DC Converter Power Modules
36–75 Vdc Input; 48.0Vdc Output; 450W Output
June 7, 2013
©2012 General Electric Company. All rights reserved.
Page 4
Feature Specifications
Unless otherwise indicated, specifications apply over all operating input voltage, resistive load, and temperature conditions. See
Feature Descriptions for additional information.
Parameter
Device
Symbol
Min
Typ
Max
Unit
Remote On/Off Signal Interface
(V
IN
=V
IN, min
to V
IN, max
; open collector or equivalent,
Signal referenced to V
IN-
terminal)
Negative Logic: device code suffix “1”
Logic Low = module On, Logic High = module Off
Positive Logic: No device code suffix required
Logic Low = module Off, Logic High = module On
Logic Low - Remote On/Off Current
All
I
on/off
1.0 mA
Logic Low - On/Off Voltage
All
V
on/off
0
0.8 V
dc
Logic High Voltage – (Typ = Open Collector)
All
V
on/off
5
V
dc
Logic High maximum allowable leakage current
All
I
on/off
50
μA
Turn-On Delay and Rise Times
(Vin=V
in,nom
, I
O
=I
O, max
, 25C)
Case 1:
T
delay
=
Time until V
O
= 10% of V
O,set
from application of V
in
with Remote On/Off set to ON
All
T
delay
120
ms
Case 2: T
delay
=
Time until V
O
= 10% of V
O,set
from application of
Remote On/Off from Off to On with V
in
already applied for at
least one second.
All T
delay
20
ms
T
rise
= time for V
O
to rise from 10% of V
O,set
to 90% of V
O,set
. All
T
rise
60
Synchronous Rectifier Activation Level and Delay*
Minimum I
OUT
to activate synch rectifier mode
I
OUT,SYNC
2.4 A
Minimum time to activate synch rectifier mode (I
OUT
> I
OUT,SYNC
) T
SYNC
1 ms
Output Voltage Overshoot
3 %
V
O, set
(I
O
=80% of I
O, max
, T
A
=25°C)
Output Voltage Adjustment
(See Feature Descriptions):
Output Voltage Remote-sense Range
(only for No Trim or Trim down application )
All V
sense
__
__
2 %V
o,nom
Output Voltage Set-point Adjustment Range (trim)
All
V
trim
28.8 --- 57.6 V
dc
Output Overvoltage Protection (T
A
=25C)
All
V
O, limit
60
65 V
dc
Over Temperature Protection
All
T
ref
115
°C
(See Feature Descriptions, Figure 19)
Input Under Voltage Lockout
V
IN, UVLO
Turn-on Threshold
All
35 36
V
dc
Turn-off Threshold
All
31 32 V
dc
Hysteresis All
2.5 3 V
dc
Input Over voltage Lockout
V
IN, OVLO
Turn-on Threshold
All
79.5
81
V
dc
Turn-off Threshold
All
80
83
V
dc
Hysteresis All
2.5 3 --- V
dc
* Note: Module has internal circuit that inhibits output synchronous rectifier mode, during module startup, until I
OUT
> I
OUT,SYNC
for
time> T
SYNC
. Once output synchronous mode is activated, module remains in synchronous rectifier mode, even if load is reduced to
0A, until module output is turned off using on/off pin or loss of input voltage.