Data sheet, General specifications, Feature specifications – GE Industrial Solutions JRCW450R Orca Series User Manual

Page 4

Advertising
background image

GE

Data Sheet

JRCW450R Orca Series; DC-DC Converter Power Modules

36–75 Vdc Input; 32.0Vdc Output; 450W Output

May 8, 2013

©2012 General Electric Company. All rights reserved.

Page 4

General Specifications

Parameter

Device

Symbol

Min

Typ

Max

Unit

Calculated Reliability based upon Telcordia SR-332 Issue 3:
Method

I

Case 3 (I

O

=80%I

O, max

, T

A

=40°C, airflow = 200 lfm, 90%

confidence)

All

FIT 214.5

10

9

/Hours

MTBF 4,661,316 Hours

Weight All

76.4

g

2.69 oz.

Feature Specifications

Unless otherwise indicated, specifications apply over all operating input voltage, resistive load, and temperature conditions. See
Feature Descriptions for additional information.

Parameter

Device

Symbol

Min

Typ

Max

Unit

Remote On/Off Signal Interface

(V

IN

=V

IN, min

to V

IN, max

; open collector or equivalent,

Signal referenced to V

IN-

terminal)

Negative Logic: device code suffix “1”

Logic Low = module On, Logic High = module Off

Positive Logic: No device code suffix required

Logic Low = module Off, Logic High = module On

Logic Low - Remote On/Off Current

All

I

on/off

1.0 mA

Logic Low - On/Off Voltage

All

V

on/off

0

1.2 V

dc

Logic High Voltage – (Typ = Open Collector)

All

V

on/off

5

V

dc

Logic High maximum allowable leakage current

All

I

on/off

50

μA

Turn-On Delay and Rise Times

(Vin=V

in,nom

, I

O

=I

O, max

,

25C)

Case 1: T

delay

= Time until V

O

= 10% of V

O,set

from application of V

in

with Remote On/Off set to ON,

All

T

delay

120

ms

Case 2: T

delay

= Time until V

O

= 10% of V

O,set

from application of

Remote On/Off from Off to On with V

in

already applied for at least

one second.

All T

delay

20

ms

T

rise

= time for V

O

to rise from 10% to 90% of V

O,set

.

All,

except -T

T

rise

50

ms

All with -T

110

ms

Output Voltage Overshoot

3 %

V

O, set

(I

O

=80% of I

O, max

, T

A

=25°C)

Output Voltage Adjustment

(See Feature Descriptions):





Output Voltage Remote-sense Range

(only for No Trim or Trim down application )

All V

sense

__

__

2 %V

o,nom

Output Voltage Set-point Adjustment Range

(trim)

All V

trim

16.0 --- 35.2 V

dc

Output Overvoltage Protection

All

V

O, limit

37

40 V

dc

Over Temperature Protection

All

T

ref

110

°C

(See Feature Descriptions, Figure 17)

Input Under Voltage Lockout

V

IN, UVLO

Turn-on Threshold

All

35 36

V

dc

Turn-off Threshold

All

31 32 V

dc

Hysteresis All

3 V

dc

Input Over voltage Lockout

V

IN, OVLO

Turn-on Threshold

All

79.5

81

V

dc

Turn-off Threshold

All

81

83

V

dc

Hysteresis All

--- 3 --- V

dc

Advertising