Data sheet, Absolute maximum ratings, Electrical specifications – GE Industrial Solutions SHHD003A0A Hammerhead Series User Manual

Page 2

Advertising
background image

GE

Data Sheet

SHHD003A0A Hammerhead Series; DC-DC Converter Power Modules

18-75Vdc Input; 5.0Vdc, 3A, 15W Output

June 26, 2013

©2012 General Electric Company. All rights reserved.

Page 2

Absolute Maximum Ratings

Stresses in excess of the absolute maximum ratings can cause permanent damage to the device. These are absolute stress ratings
only, functional operation of the device is not implied at these or any other conditions in excess of those given in the operations

sections of the data sheet. Exposure to absolute maximum ratings for extended periods can adversely affect the device reliability.

Parameter

Device

Symbol

Min

Max

Unit

Input Voltage (Continuous)

All

V

IN

-0.3 80

Vdc

Transient (100ms)

All

V

IN, trans

-0.3 100

Vdc

Operating Ambient Temperature

All

T

A

-40 85

°C

(see Thermal Considerations section)

Storage Temperature

All

T

stg

-55 125

°C

Altitude* All

4000 m

I/O Isolation Voltage (100% factory Hi-Pot tested)

All

2250 Vdc

* For higher altitude applications, contact your GE Sales Representative for alternative conditions of use.

Electrical Specifications

Unless otherwise indicated, specifications apply over all operating input voltage, resistive load, and temperature conditions.

Parameter

Device

Symbol

Min

Typ

Max

Unit

Operating Input Voltage

All

V

IN

18

24/48

75 V

dc

Input No Load Current

V

IN

= 24V

dc

, (I

O

= 0, module enabled)

All

I

IN,No load

40

mA

V

IN

= 48V

dc

, (I

O

= 0, module enabled)

All

I

IN,No load

30

mA

Input Stand-by Current

All I

IN,stand-by

4

6

mA

(V

IN

= 24 to 48V

dc

, module disabled)

Maximum Input Current (V

IN

=18V

dc

, I

O

=I

O, max

) All

I

IN,max

1.1

A

dc

Inrush Transient

All

I

2

t

0.05 A

2

s

Input Reflected Ripple Current, peak-to-peak

(5Hz to 20MHz, 12μH source impedance; V

IN

=0V to 75V

dc

, I

O

= I

Omax

;

see Test configuration section)

All

30

mA

p-p

Input Ripple Rejection (120Hz)

All

60

dB

EMC, EN55022

See EMC Considerations section

CAUTION: This power module is not internally fused. An input line fuse must always be used.

This power module can be used in a wide variety of applications, ranging from simple standalone operation to being part of
complex power architecture. To preserve maximum flexibility, internal fusing is not included; however, to achieve maximum safety

and system protection, always use an input line fuse. The safety agencies require a fast-acting fuse with a maximum rating of 3 A
(see Safety Considerations section). Based on the information provided in this data sheet on inrush energy and maximum dc input
current, the same type of fuse with a lower rating can be used. Refer to the fuse manufacturer’s data sheet for further information.

Advertising