Configuration, Bringing the vsd onto the network, Starting the vsd – GE Industrial Solutions LONWORKS Interface Card OPC-G11S-LON User Manual

Page 15: Vsd network interface, Status leds, Configuration 13, Bringing the vsd onto the network 13, Starting the vsd 13, Vsd network interface 13, Status leds 13

Advertising
background image

Document number: 80-0098

Data subject to change without notice 5/00. © General Electric Company



Configuration

All configuration data is stored in a master file in the VSD. This is so that, whether

you configure the VSD through the keypad or the Interface Card, you will be

looking at the same configuration settings.

Bringing the VSD onto the Network

To add the VSD node to the building network:

‡ 8VLQJ \RXU QHWZRUN WRRO IRU H[DPSOH /RQ0DNHU &LUFRQ 6\VWHP ,QWHJUDWRU HWF DGG WKH 96'

WR \RXU QHWZRUN

The first time you try to bring the VSD onto the network an Er4 type error may

occur on the VSD. If this happens, press the Reset button on the VSD keypad; when

the reset is complete the drive will be ready to configure.

Starting the VSD

The network variable nvidrvSpeedSetpt sets the speed of the drive. (See Tables 1-3

for network variable descriptions.)

VSD Network Interface

After the VSD is online you can monitor the it and set the configuration variables

that represent the most common functions used in HVAC applications of VSDs.

To get the current configuration parameters from the VSD to Node Editor you have

to upload them after the VSD is online.

Status LEDs

The L

ON

W

ORKS

interface card has six LEDs that show the communication status of

the VSD. Figure 5 shows the LED functions.

Advertising