Output voltage 120vac single phase, Proceed as follows: lanpro, U 5/6kva: step 4-6, lanpro – GE Industrial Solutions LP11U Series UPS - PDU option User Manual

Page 5: For lanpro

Advertising
background image

Page 5 of 7

LanPro PDU- PDU-IXXX-XXX
Installation Instructions 5/02/04
2020000502

Copyright 2003 GE Zenith Controls
All Rights Reserved
2501 Pecan Street, Bonham TX 75418
903-640-0555 Fax: 903-640-0535

between terminals 2 and 3. An extra link was
delivered with the unit (in a plastic bag) to enable
other output voltages (5/6kVA models only). The
following voltages are available: 120, 208, 220, 230,
240VAC. See the 'Available Output Voltages'
section (4.4.3) of the Installation/User Manual for
hardware configurations for each output voltage.

10)

Connect the PDU terminal block wires to the
LanPro U output terminal block as follows:

OUTPUT VOLTAGE: 120VAC SPLIT-PHASE,
208/220/230/240VAC (FIG. 10)

This is the off-factory setting. There is a link between
terminal 2 and 3.

1. Connect the output wires to the terminals 1 (L1)

and 4 (L2).


2. Connect the neutral wire (N) to terminal 2.

3. Connect the ground wire to terminal 5. Ground
connection is essential!

OUTPUT VOLTAGE 120VAC SINGLE PHASE

1.

The factory setting of the output tap (208Vac)

must be changed to 240Vac. Follow the
procedure as described in section 4.4.3.2 steps
1.1 and 1.2 of the LanPro U users manual.

2. Remove the link between terminals 2 and 3.

3.

Proceed as follows:

LanPro

®

-U 5/6kVA: step 4-6,

LanPro

®

-U 8/10kVA: step 7-10.

For LanPro

®

-U 5/6kVA: (FIG. 11)

4. Place this link between terminals 1

and 2.


5. Place the extra link (delivered with the

unit) between terminals 3 and 4.

N

gnd

L1 L2

gnd

1

2

4

3

7

6

5

8

JUMPER
SUPPLIED WITH
LANPRO. INSTALL
IN ACCORDANCE
WITH LANPRO U
INSTALLATION/US
ER MANUAL.

(BLACK)

(WHITE)

(GND)

L1

L2

N

N

gnd

L1 L2

gnd

1

2

4

3

7

6

5

8

JUMPERS
SUPPLIED WITH
LANPRO. INSTALL
IN ACCORDANCE
WITH LANPRO U
INSTALLATION/US
ER MANUAL.

(BLACK)

(WHITE)

(GND)

L1

L2

N

N

gnd

L1 L2

gnd

1

2

4

3

7

6

5

8

L1

L2

N

(BLACK)

(WHITE)

(GND)

JUMPERS
SUPPLIED WITH
LANPRO. INSTALL
IN ACCORDANCE
WITH LANPRO U
INSTALLATION/US
ER MANUAL.

FOR 8KVA AND
10KVA UNITS, USE
TWO
CONDUCTORS
FOR BOTH THE L1
AND NEUTRAL
CONNECTION.

Fig. 10

Fig. 11

Fig. 12

OR

OR