GE Industrial Solutions PowerVac with ML-18 or ML-18H Mechanism User Manual

Page 36

Advertising
background image

36

TABLE 2 MEASUREMENTS

ITEM

BREAKER

CL. SPRING

OP. SPRING

MEASUREMENT

PG.

CONTACT

WIPE

OPEN

CLOSED

CHARGED
CHARGED

DISCHARGED

CHARGED

MEASURED BETWEEN EROSION

DISK AND WIPE INDICATOR

11

CONTACT

GAP

OPEN

CLOSED

CHARGED
CHARGED

DISCHARGED

CHARGED

MEASURE THE TRAVEL OF THE

OPERATING ROD INSULATOR

11

CONTACT

EROSION

CLOSED

DISCHARGED

CHARGED

MEASURE BETWEEN EROSION

DISK AND REFERENCE ARM

11

TRIP

COIL

CLOSED

DISCHARGED

CHARGED

MEASURE BETWEEN PLUNGER

BUTTON AND COIL HOUSING

12

CLOSE

COIL

OPEN

CHARGED

DISCHARGED

MEASURE BETWEEN PLUNGER

BUTTON AND COIL HOUSING

12

CONTROL

SWITCHES

OPEN

DISCHARGED

DISCHARGED

DEPENDS ON SWITCH TYPE

SEE SECTION 8.6

12

TIMING

SEE SECTION 12

18

CONTACT

SPEEDS

SEE SECTION 13

19



TABLE 3 ADJUSTMENTS

ITEM

BREAKER

CL. SPRING

OP. SPRING

MEASUREMENT

PG.

CONTACT

WIPE

CLOSED

CHARGED

CHARGED

ADJUST OPERATING ROD TO

OBTAIN REQUIRED DIMENSION

23

CONTACT

GAP

OPEN

DISCHARGED

DISCHARGED

ADVANCE OR RETARD GAP

ADJUSTING NUTS TO SET GAP

23

CONTACT

EROSION

CLOSED

DISCHARGED

CHARGED

ALIGN REFERENCE ARM WITH DISK

ON NEW UNITS ONLY

11

TRIP

COIL

CLOSED

DISCHARGED

CHARGED

TURN ADJUSTING NUT TO OBTAIN

REQUIRED DIMENSION

24

CLS. LATCH

STOP BOLT

FOR -0, -1

& -2 BKRS

OPEN

CHARGED

DISCHARGED

½ TO ¾ TURN OUT FROM SPRING

DISCHARGE POINT

24

CLS. LATCH

STOP BOLT

FOR -3 BKRS

OPEN

CHARGED

DISCHARGED

NO ADJUSTMENT

24

CLOSE

COIL

OPEN

CHARGED

DISCHARGED

TURN ADJUSTING NUT TO OBTAIN

REQUIRED DIMENSION

24

CONTROL

SWITCHES

OPEN

DISCHARGED

DISCHARGED

ADJUST MOUNTING BRACKET TO

OBTAIN REQUIRED DIMENSION

12

OVER-

TRAVEL

STOP

OPEN

DISCHARGED

DISCHARGED

SEE SECTION 16.3, ITEM 4 FOR

ADJUSTMENT

24

Advertising