Dv-300, Av-300, Dgf card – GE Industrial Solutions 6KCV300CTI User Manual

Page 8

Advertising
background image

GEI-100275

6KCV300CTI - 11/97

7

DV-300

Jumpers name

function

Default configuration

Using 6KCV300CTI

S12/S13

Insertion/disconnection of

the terminating resistor

ON = Inserted

ON = Inserted

(On the first and the last drop of the

net)

S15

Insertion/disconnection of

RX channel

ON = Inserted

ON = Inserted

S29/S30

Insertion/disconnection of

TX-RX TTL level

OFF

Not Active

OFF

Not Active

S18/S19

Selection internal/external

supply for RS485 interface

A-C Position

External (pin 5-9)

B-C Position (Internal)

A-C Position

(External)

B-C Position

(Internal)

AV-300

Jumpers name

function

Default configuration

Using 6KCV300CTI

S12/S13

Insertion/disconnection of

the terminating resistor

ON = Inserted

ON = Inserted

(On the first and the last drop of

the net)

S15

Insertion/disconnection of

RX channel

ON = Inserted

ON = Inserted

S31/S32

Insertion/disconnection of

TX-RX TTL level

OFF

Not Active

OFF

Not Active

S18/S19

Selection internal/external

supply for RS485 interface

A-C Position

External (pin 5-9)

B-C Position (Internal)

A-C Position

(External)

B-C Position

(Internal)

DGF card

Jumpers name

function

Default configuration

Using 6KCV300CTI

S23/S24

Insertion/disconnection of

the terminating resistor

ON = Inserted

ON = Inserted

(On the first and the last drop of

the net)

S25

Insertion/disconnection of

RX channel

ON = Inserted

ON = Inserted

S26/S27

Insertion/disconnection of

TX-RX TTL level

OFF

Not Active

OFF

Not Active

S21/S22

Selection internal/external

supply for RS485 interface

OFF Position

External (pin 5-9)

ON Position (Internal)

OFF Position

(External)

ON Position

(Internal)

Advertising