3 power supply, 4 leds, 3 power supply 2.4 leds – GE Industrial Solutions 6KCV301PDP33 Profibus - DP Bus for AV300i User Manual

Page 9

Advertising
background image

2

9

——————

HARDWARE DESCRIPTION

——————

Profibus-DP

3.

The 6KCV301PDP33-Drive link cable is connected to the XT connector
on the 6KCV301PDP33-card.

4.

The bus terminating resistors are connected or disconnected through the
S2 dip switch.

The last physical card in network shall have such resistors connected in
case the connector in use should not contain terminating resistors itself.
ON = connected

OFF = disconnected.

5.

The S1 dip switch determines the Slave address.

The addresses “0” and “1” are reserved to the Master and can not be
used. The switch S1-8 is not significant for the address and must always
be set to OFF. The address is only detected when the card is switched on.
If the address has been modified, the Profibus-DP interface card has first
to be switched off and then on in order assume the new address.

6.

Connect the Bus cable to XS1 or XS2 connectors.

7.

Switch on the drive.

8.

The LEDs +5V and +5VE light up.

9.

The LED DEA lights up when the communication enters in the Data
Exchange Phase.

2.3 POWER SUPPLY

The power supply is provided by the XT connector which is also used to
transfer data between the 6KCV301PDP33 card and the drive regulation card.

Current draw: 350 mA

2.4 LEDS

+5V

+5V power supply.

RST

Reset active.

DEA

Data Exchange Phase active.

+5VE +5V power supply on the RS 485 driver side galvanic isolated.

Advertising