Analytical Industries GPR-2500 A Oxygen Analyzer User Manual

Page 16

Advertising
background image



16

The 4-20mA signal output, power fail, alarm relay contacts, and, output connections are made to a terminal block

mounted on a PCB located in the bottom half of the front cover of the enclosure and appear upside when the
hinged enclosure is open and front cover swings up as illustrated below. The PCB also includes a transformer to

power the alarm relays. The main processing display PCB is located in the upper half of the front cover of the

enclosure.
To assure proper grounding, connect the 4-20mA signal output to the external device (PLC, DCS, etc.) before

attempting any zero or span adjustments.
Procedure:
1. Remove the four (4) screws securing the

protection Plexiglas guard.

2. Separate the shielding from the wires of

the cable.

3. Ensure the positive and negative

terminals of the incoming 24VDC power
supply are connected to the appropriate

terminals of the barrier strip as marked.

4. The output connections enter the GPR-

2500A from the hole provided in the right

side of the enclosure. Note: The user is
responsible for providing the appropriate

conduit and fittings.

5. Connect the shielding of the cable to the

ground screw. Note: The terminals snap

together, making it possible to detach the

section with the ground, install the
shielded cable and reinstall.

6. The 4-20mA current output is obtained

by connecting the current measuring

device between the positive and negative

terminals of the OUTPUT 4-20mA.

7. To check the signal output of the 4-20mA

E/I integrated circuit connect an ammeter

as the measuring device and confirm the

output is within +0.1mA of 4mA.

8. Replace the protective Plexiglas guard

and secure.


Caution:
To assure proper grounding,

connect the 4-20mA signal output to the

external device (PLC, DCS, etc.) before

attempting any zero or span adjustments.