TROUBLESHOOTING REFERENCE

SYMPTOM

POSSIBLE CAUSE

SOLUTIONS

ON/OFF switch is
switched on, LED does

not light, buzzer is off, no
AC output.

There is no DC power from

the input terminals

1. Check the continuity of the DC power input, ensure all
batteries are working or DC power supply is on.

2. Check that the battery inline fuse is intact. Replace if
blown.

3. Check that all connections in the power bank battery

array are tight.

Polarity of the DC input has
been reverse connected

Correct the polarity of the input connections, check and

replace any blown up fuses. If unit remain unresponsive,
permanent damage may have occurred, please contact
technical repair.

Buzzer sounded once

only when switch on,
power LED on, no AC

output.

1. Loose AC output

connections.
2. Short circuit on AC output

load.

1. Ensure fully plugged in on AC output sockets.

2. Ensure connected load is not faulty.
Contact technician/retailer is problem unsolved.

Buzzer sounds 2 times

and red light flashes 2

times every 8 seconds

Voltage across the DC input

terminals dropped below
10.8± 0.2Vdc (on 12V input

inverter), 21.6± 0.4Vdc (on
24V input inverter).

1. Check battery level, if it is low please recharge before

continuing use.

2. On the battery cables used check the cross-section
area of the conductor is no thinner than recommended,

use thicker cables if required. Also avoid connecting
inverter to input power at a long distance as voltage

drops along the length of the cable.

3. Ensure input connections are tight.

Buzzer sounds 3 times

and red light flashes 3
times every 8 seconds

Voltage across the DC input
terminals dropped below

critical range 10.2± 0.2Vdc (on

12V input inverter),
20.4± 0.4Vdc (on 24V input

inverter).

1. Check battery level, if it is low please recharge before
continuing use.
2. On the battery cables used check the cross-section

area of the conductor is no thinner than recommended,
use thicker cables if required. Also avoid connecting

inverter to input power at a long distance as voltage

drops along the length of the cable.
3. Ensure input connections are tight.

Buzzer sounds 4 times

and red light flashes 4

times every 8 seconds

Input DC power is higher than

inverter’s maximum limit
15.5± 0.2Vdc (on 12V input

inverter),
31± 0.4Vdc (on 24V input
version)

1. Check and ensure the DC input voltage across the
input terminal is no more than 15/30Vdc.

2. Ensure that the maximum charging voltage of the
battery charger /alternator / solar charge controller is no

more than 15/30Vdc
3. Ensure that an un-regulated DC power supply and
charger are not used to charge the power bank while in

use.

Buzzer sounds 5 times
and red light flashes 5

times every 8 seconds

System overheating, inner
temperature has reached 75°C

1. Switch off for 15 min to cool down the unit before

switch back on. Check that the fan is working. If not, the
fan/fan control circuit may be defective, please contact

retailer.
2. If the fan works, ensure that the ventilation slots on

the front and back of the inverter are not obstructed

3. If the fan is working and ventilation ports are not
obstructed, check that enough air space is available for

ventilation and cooling. Also check that the air
temperature is less than 45ºC which is the maximum limit

for the inverter to work in.
4. Reduce the load to reduce the heat output.
5. If inverter is under full load, an external fan will help to

cool down the unit.

Red light constantly

flashing when switched
on

The load is higher than the

inverter’s rated continuous
power

The appliance requires an inverter with a higher rated

power to start up