NOTICE:
Never use the valve as a form of piping support. Support the valves and piping according
to the local building code. Failure to follow these instructions may result in property
damage.

Install flanged connections

• Flanged Ultra Setter

TM

pressure independent control valves are not furnished with

companion flanges, gaskets, nuts, and bolts.

• Check and make sure the gaskets do not extend into the inside diameter of the pipe.

This will cause a blockage and affect the performance of the Ultra Setter

TM

.

• Check connections for leaks.

Install the actuator

Figure 1: Actuator Positioning

NOTICE:
To install an actuator on a valve already in line, close the shutoff valves (upstream first,
then downstream) in the piping or turn off the pump. This procedure allows the
differential pressure in the valve to drop.

Before installing the actuator, set the flow rate on the Ultra Setter

TM

pressure independent

balancing control valve. Follow the curve information in the product submittal to find the
required minimum differential pressure for the desired flow rate.
1. Grip the flats of the valve stem with a 7mm wrench and turn until the flow rate on the

adjacent GPM dial is in line with the indicator on the valve body.

Installation

Ultra Setter

Pressure Independent Control Valves Installation, Operation and Service Manual

9