Attach insulation – Bell & Gossett V1000840 Ultra Setter Large Pressure Independent Control Valves User Manual

Page 12

Advertising
background image

NOTICE:
Must disconnect all actuator stem connections and anti-rotation devices that may be
found on the actuator before rotating the actuator. Failure to do so will change the
maximum GPM flow rate setting of the valve.

2. Assemble actuator to valve and wire connections per actuator manufacturer's

instructions.

Attach insulation

To maximize energy savings, attach insulation to the valve after the system has been
balanced. Tape or other acceptable means can be used to secure the insulation to the
valve. The insulation must not cover the actuator.

Installation

10

Ultra Setter

Pressure Independent Control Valves Installation, Operation and Service Manual