Maintenance

Precautions

WARNING:

• All procedures must be performed by qualified personnel.
• When the process fluid is hazardous, thermal (hot or cold), or corrosive, take extra

precautions. Employ the appropriate safety devices and be prepared to control a
process media leak.

• Always wear protective clothing and equipment to safeguard the eyes, face, hands,

skin, and lungs from the particular fluid in the line.

Valve inspection

Periodically inspect the valve for signs of leakage or corrosion.

WARNING:
Risk for property damage, serious personal injury or death. You must replace the valve if
corrosion or leakage is found.

Service P/T Ports

The P/T readout ports and drain plugs come pre-assembled with a leading industrial
thread sealant, Loctite, and are tightened to appropriate levels. Any field adjustment of
factory installed components breaks the original thread seal and could cause leakage.
This adjustment necessitates the removal, cleaning, and resealing of those parts per the
following instructions.
1. Remove the desired component from the valve.
2. Clean off all of the old thread sealant using a wire brush and gentle abrasion if

necessary.
If the component or valve appears to have been damaged, replace it.

3. Starting with the second thread of the NPT male valvecomponent, apply a 360º bead

of Loctite 567 thread sealant/lubricant as shown. Follow Loctite handling precautions
as noted on the product label.

4. If Loctite is not available, it is recommended that you use RectorSeal No. 5 pipe thread

sealant for all non-glycol based applications, or any PTFE thread sealing tape. Be sure
to follow the manufacturer-specific handling precaution and application instructions
as noted on the product label.

5. Thread component into the valve until it is finger tight.
6. Apply torque to the following specification:

Size

Type

Torque

1/4” NPT

P/T Readout Port, drain plug

9.0 ft-lbs. + 3.0 ft-lbs. / 0

Maintenance

12

Ultra Setter

Pressure Independent Control Valves Installation, Operation and Service Manual