John Wood Power Vent (Non-ENERGY STAR qualified models) User Manual

Page 11

Advertising
background image

Venting terminations and sizing

• Refer to Figure 8 and Table 2 for vent pipe materials

and sizing. Examples of the vent terminations are
shown in Figures 9 and 10. If the installation requires a
vent riser, suitable drainage must be provided to ensure
condensation does not accumulate. Termination
through a roof is shown Figure 11.

• G/JW 40, 50 and 60-gallon heaters are supplied with a

50mm (2 in.) termination elbow and (2) plastic "rodent
screens" (see Figure.7). The screen is required to keep
foreign objects, rodents and small birds from entering
the venting system and only one (1) screen is to be
installed in the termination elbow. These screens have
been sized to ensure maximum energy efficiency of the
venting system based on the "equivalent length" of the
vent piping. How to determine the equivalent length is

shown in Figure 8. The appropriate screen is to be
installed into the end of the termination elbow and
secured with a small amount of silicone sealant. This
will allow for easy removal for inspection and cleaning.
For installations using 76mm (3 in.) venting, use the
76mm (3 in.) termination elbow and screen.

• G/JW5065 high input models are supplied with a 76mm

(3 in.) termination elbow that includes a steel mesh
rodent screen.

– 11 –

Example for calculating equivalent feet.
Section “A” . . . . 0.15m . . (0.5 ft.)
90° elbow . . . . . 1.83m . . (6.0 ft.)
Section B . . . . . 0.31m . . (1.0 ft.)
45° elbow . . . . . 0.91m . . (3.0 ft.)
Section C . . . . . 0.46m . . (1.5 ft.)
45° elbow . . . . . 0.91m . . (3.0 ft.)
Section D . . . . . 4.57m . (15.0 ft.)
Total Equivalent 9.14m . (30.0 ft.)
Based on this example use the (fully open) rodent
screen for vent length greater than 6.1 equivalent
metres (20 equivalent ft.) (see Figure 7).

NOTE: VENT PIPE MUST BE SUPPORTED EVERY 1.2m (4 ft.). TO PREVENT VIBRATION, USE ISOLATION
PADS WHEN ATTACHING STRAPS TO FLOOR JOISTS, WALLS OR CEILINGS.

PVC ADAPTER
(SUPPLIED)

STRAP

150mm

(6 in.)

MIN.

45°

ELBOW

90°

ELBOW

RODENT SCREEN

(INSTALL INTO

ELBOW)

Figure 8

General Venting Layout

TERMINATION

ELBOW

GROUND LEVEL OR

MAXIMUM SNOW

LINE*

WATER

HEATER

MODEL

SUFFIX

VENT PIPE

SIZE

PRESSURE

SWITCH

SETTING

* VENT

MATERIAL

(SCHEDULE 40)

MAXIMUM EQUIVALENT

VENT LENGTH

MINIMUM EQUIVALENT

VENT LENGTH

NVH,

PVH

50mm (2 in.)

- 0.15 in. w.c.

(-0.037 kPa)

PVC**, CPVC

15.2m (50 ft.) +
termination elbow

0.76m (2.5 ft.) + one 90°
elbow + termination elbow

NVH,

PVH

76mm (3 in.)

- 0.15 in. w.c.

(-0.037 kPa)

PVC**, CPVC

24.4m (80 ft.) +
termination elbow

15.2m (50 ft.) +
termination elbow

G/JW5065

SNV,

SPV

76mm (3 in.)

- 0.55 in. w.c.

(-.137 kPa)

PVC, CPVC

15.2m (50 ft.) +
termination elbow

0.91m (3 ft.) + one 90°
elbow + termination elbow

G/JW5065

LNV

76mm (3 in.)

- 0.50 in. w.c.

(-.124 kPa)

PVC, CPVC

19.8m (65 ft.) +
termination elbow

6.9m (20 ft.) + termination
elbow

G/JW40,

50, 60

Notes:
1. Use long radius elbows where possible. Minimum dis-

tance between 90º elbows should be 150mm (6 in.).

2. *Check local codes to determine which materials are

allowed in your area.

3. **Pipe assembly adapter must be used with PVC

venting material (see Figures 13, 14 & 15).

Table 2

Allowable Vent Lengths and Materials (Vert. and Horiz.).

Equivalent lengths of straight pipe for various elbows using
Schedule 40 PVC and CPVC.

Size

Type

Short Sweep/

Short Radius

Long Sweep/

Long Radius

50mm (2 in.)

90° elbow

2.44m (8 ft.)

1.52m (5 ft.)

76mm (3 in.)

90° elbow

2.44m (8 ft.)

1.52m (5 ft.)

50mm (2 in.)

45° elbow

0.91m (3 ft.)

0.76m (2.5 ft.)

76mm (3 in.)

45° elbow

1.22m (4 ft.)

1.07m (3.5 ft.)

Advertising