Vent termination – John Wood Superflue Power Vent (before FVIR technology) User Manual

Page 6

Advertising
background image

-4-

1. EACH 2” (50mm) 90° ELBOW USES 5 EQUIVALENT FEET (1.5 METERS).
2. EACH 3” (75mm) 90° ELBOW USES 7 EQUIVALENT FEET (2.1 METERS).
3. ONE 2” (50mm) 45° LONG-RADIUS ELBOW IS EQUIVALENT TO 3’ (.9 METERS) OF 2” (50mm) STRAIGHT PIPE.
4. ONE 3” (75mm) 45° LONG RADIUS ELBOW IS EQUIVALENT TO 4’ (1.2 METERS) OF 3” (75mm) STRAIGHT PIPE.
5. MINIMUM DISTANCE BETWEEN ELBOWS IS 6” (150mm)
6. DO NOT MISMATCH VENTING MATERIALS.

Table VI

In the U.S.:

the vent terminal shall terminate not less than 3’
above any forced air inlet duct.

the vent terminal shall terminate not less than 4’
below, 4’ horizontally, or 1’ above any door, window
or gravity air inlet into any building.

the vent terminal shall be located not less than 1’
above grade.

the vent terminal shall not exit into a public walk-
way.

in locations where high snow accumulations occur,
or where the exit from the building is less than 1’
above grade, a vent riser may have to be installed.
See Figure 6 for recommended practices.

Vent Termination

1. Drill a hole through the exterior wall, slightly larger

than the vent piping, to allow for final alignment of
the vent piping to the heater.

2. Attach the termination elbow to a short length of vent

pipe – approximately 2’ minimum, 5’ maximum.

3. Push this pipe through the wall from the outside

until the joint with the elbow is within 1” – 2” of the
outside face of the wall.

4. Point the elbow down and hold the pipe temporari-

ly in position with a small wedge or a splinter of
wood.

5. Proceed to construct vent pipe connections to the

water heater.

CAULK

CAULK

ATTACH 90° TERMINATION
ELBOW

12” MIN.

GROUND LEVEL OR MAXIMUM SNOW LINE

ILLUSTRATION OF VENT TERMINATION

EXTERIOR INSTALLATION

Figure 3 - 1

ALLOWABLE VENT LENGTHS AND MATERIALS

(BOTH VERTICAL AND HORIZONTAL VENTING)

WATER

HEATER

MODEL

SUFFIX

NVH, PVH

-0.15 in.

wc

CPVC, ABS

VENT PIPE

SIZE

PRESSURE

SWITCH

SETTING

(in . W.C.)

VENT

MATERIAL

(SCHEDULE 40)

in.

(mm)

2”

(50)

NVH, PVH

- 0.15 in.

wc

CPVC, ABS

3”

(75)

G40
G50
G60

SNV, SPV

- 0.55 in.

wc

CPVC, PVC, ABS

3”

(75)

G5065

MAXIMUM EQUIVALENT

VENT LENGTH

50 FEET (15.2 METERS)
+TERMINATION ELBOW

80 FEET (24.4 METERS)
+TERMINATION ELBOW

50 FEET (15.2 METERS)
+TERMINATION ELBOW

3 FEET (0.91 METERS) +

ONE 90° ELBOW +TERMI-

NATION ELBOW

50 FEET (15.2 METERS)
+TERMINATION ELBOW

2

1

/

2

FEET (0.76 METER) +

ONE 90° ELBOW +TERMI-

NATION ELBOW

MINIMUM EQUIVALENT

VENT LENGTH