– 27 –

The self-diagnostic test has
detected that the water tem-
perature sensor is either open
or short circuited.

1. Turn the power off for 10-20 seconds then on again to clear this

error code.

2. If no wiring problems are found the control must be replaced.

The self-diagnostic test has
detected one of the tempera-
ture adjust buttons stuck
closed.

1. Make sure that there are no objects leaning against the front of the

control.

2. Lightly press and release each of the buttons once.
3. If the above actions do not clear the error, the control will continue

to regulate water temperature at the last setting, but you will not be
able to change settings unless you replace the control.

Error 12

Error 13

Error 7

The self-diagnostic test found
a problem with the gas valve
driver circuit.

1. Cycle power to the water heater “OFF” for 10 seconds and then

back “ON”.

2. If the above step did not clear the error, the control must be

replaced.

The self-diagnostic test has
detected a problem with the
internal microcomputer.

1. Cycle the external power “OFF” for 10 seconds and then back “ON”.
2. If the above step does not clear the error, the control must be

replaced.

The self-diagnostic test has
detected a problem with the
internal circuit.

1. Cycle the external power “OFF” for 10 seconds and then back “ON”.
2. If the above step does not clear the error, the control must be

replaced.

Flame signal sensed out of
proper sequence.

1. Insure flame sensor ceramic insulator is not cracked.
2. Turn power off for 10-20 seconds, and then on again to clear the

error code.

3. Replace the control.

Error 8

Error 9

Error 10

The high temperature thermal
cutoff is open.

1. Turn the power off for 10-20 seconds then on again to clear the

error code.

2. Replace the control.

Error 11

SYMPTOM

POSSIBLE CAUSE(S)

CORRECTIVE ACTION

Table 4 (cont’d) Intelli-Vent

TM

System Error Codes.