John Wood Superflue Power Vent (75 Gallon) User Manual

Page 34

Advertising
background image

– 34 –

STEP

CHECK THAT:

POSSIBLE PROBLEM

CORRECTION

11.

Gas valve opens, main burner
comes on

- Poor electrical connection on

control

- Flashing red LED light from:

insufficient gas pressure

- flame rod out of position

- flame rod oxidized (low signal) or

broken (no signal)

- Safety shut down by pressure

switch or high limit switch.
Blower continues to run but
heater will not operate

- Check power supply and termi-

nal connections

- Correct gas supply and burner

manifold pressures

- Reposition rod (rod tip should be

level with or slightly above the
top of the burner)

- Unplug flame sensor wire and

connect micro amp meter.
Current should be greater than
0.7 micro amps. Remove oxida-
tion (if present) with steel wool.
Replace rod if broken or signal
insufficient.

- See above information on pres-

sure switch or high limit switch

- Check for debris that have may

entered combustion chamber or
venting