Vent Clearances

INSIDE CORNER

DET

AIL

FIXED

CLOSED

OPERABLE

FIXED

CLOSED

OPERABLE

Vent terminal

Air supply inlet

Area where is not permitted

Gas meter / regulator

Canada

Direct vent and other than Direct Vent

A

Clearance above grade, veranda, porch, deck, or balcony.

1 foot

30.5cm

B Clearance to window or door that may be opened

3 feet

91.5cm

C

Clearance to permanently closed window

*

D

Vertical clearance to ventilated soffit located above the vent termi-
nator within a horizontal distance of 2 feet (61cm) from the center
line of the terminator.

*

E

Clearance to unventilated soffit

*

F

Clearance to outside corner

*

G

Clearance to inside corner

*

H

Clearance to each side of center line extended above meter/regula-
tor assembly

3 feet

91.5cm

I

Clearance to service regulator vent outlet.

3 feet

91.5cm

J

Clearance to non-mechanical air supply inlet to building or the com-
bustion air inlet to any other application

3 feet

91.5cm

K

Clearance to mechanical air supply inlet.

6 feet

1.8m

L

Clearance above paved sidewalk or paved driveway
located on public property.

7 feet

2.1m

M

Clearance under veranda, porch deck, or balcony.

1 foot

30.5cm

* For clearances not specified in CSA-B149.1, please use clearances in accordance with local installation codes and

the requirement of the gas supplier.