Models, Ac input, Ac output – Alpha Technologies AMP24 HP User Manual

Page 31

Advertising
background image

29

Doc. #: 0260011-J0 Rev B

The recommendations in Table G are for reference only. A registered professional engineer

must review and approve or modify these recommendations in compliance with applicable

national and local electrical and building codes.

NOTE:

Table G — 18kVA and 13.5kVA, 120V/208V 3-Phase

Systems

Models

AMPS24-3-18-i3

(4i Shelf)

0260012-205

AMPS24-3-13.5-H3

(3i+1R Shelf)

0260011-105

AC Input

AC Input Voltage

120/208V

120/208V

Full Load AC Input Current

(per phase)

56A

59A

AC Input poles & wiring

4 w + G

4 w + G

Wiring

3Ф Wye

3Ф Wye

SCCR

1600A

1600A

Recommended

AC input Breaker/fuse

(Note: 2)

80A

80A

Recommended

AC Input Wire size,

90ºC copper (Note 1)

NEC 50ºC

4

4

CEC 50ºC

3

3

Total AC Output (Max)

18 kVA/ 14.4kW

13.5 kVA/ 10.8kW

AC Output

AC Output Voltage

120/208V

120/208V

AC Output poles & wiring

4 w + G

4 w + G

Wiring

3Ф Wye

3Ф Wye

AC Output Current (per Phase)

50A

37.5A

Installed Inverter Output

Circuit Breaker 100% rated

70A

70A

Recommended

AC Input Wire size,

90ºC copper (Note 1)

NEC 50ºC

4

4

CEC 50ºC

3

3

AC Input & Output

connection terminals

Box lugs are rated for both aluminum or copper wire, #2/0 to #6

AWG. Fasten clamping screw to 120 in-lbs (14 N-m)

Note 1: Inverter AC Input & AC Output connections: Calculations based on full load and charging current, 0.8

derating with 5 current carrying conductors, (L1,L2,L3,2XN) due to possible high harmonic content

load. Temperature correction factor for 50C applied.

Note 2: Maximum AC Utility Service protection feeding the AMPS24 is 150A. Actual supply circuit breaker

must be sized appropriately for the supply wire used. Consult your local and national electrical

codes. Double neutral is strongly recommended for AC output wiring (and AC input wiring to the

MBS) for 3Ф systems with significant non-linear (ie rectified capacitive) loads. Since the AC input to

systems without MBS is power factor corrected, AC wiring to systems without MBS does not require

double neutral wiring.