3.2.1 Terminal Block Input and Output Wiring

20

3. INSTALLATION

CFR 1500, CFR 2000, CFR 2500 and CFR 3000

Terminal Block Input

Frequency

Voltage*

L

N

60Hz

120VAC

120VAC

Neutral

50Hz

230VAC

230VAC

Neutral

60Hz

208VAC

Ш1

Ш2

60Hz

240VAC

Ш1

Ш2

WARNING: Overcurent protection for the AC output circuit must be

provided

at the time of installation

CFR 1500, CFR 2000, CFR 2500 and CFR 3000

Terminal Block output

Frequency

Voltages*

L1

N

L2**

60Hz

120 / 208 VAC

120VAC

Neutral

208VAC

60Hz

120 / 240 VAC

120VAC

Neutral

240VAC

50Hz

230VAC

Not Used

Neutral

230VAC

* CAUTION: Refer to the nameplate voltage and frequency ratings
affixed to the unit. This power supply was wired for this particular
voltage configuration when it was shipped from the factory.

**Units shipped as 60Hz, single 120V output, do not use L2.

5. RS-232 TERMINAL COMMUNICATION

“MAINTENANCE PARAMETERS” allow you to customize UPS detection

and warning characteristics. Normally, there should be no need to change these
factory settings.

CAUTION: If any of these parameters are changed, it is vital to thoroughly
test the UPS since an improper adjustment can render the unit useless.
Since each parameter is viewed through reference numbers (1 - 16) and
translated into a scale of “reasonable” adjustments, an increase or decrease
of 2 - 3 reference numbers will have a noticeable affect. If you have
questions, contact Alpha prior to making any adjustment.

Fast Detect Lo Ref

Increasing this value will make the UPS more sensitive to a fast, low

amplitude line disturbance (glitch).

Fast Detect Hi Ref

Increasing this value will make the UPS more sensitive to a fast, high

amplitude line disturbance (spike).

Medium Detect Lo Ref

Increasing this value will make the UPS more sensitive to a slow, low

amplitude line disturbance (sag).

Medium Detect Hi Ref

Increasing this value will make the UPS more sensitive to a slow, high

amplitude line disturbance (surge).

Slow Detect Lo Ref

Increasing this value will make the UPS more sensitive to a slow, low

amplitude line disturbance (brownout) by raising the brownout detection
level.

NOTE: The Slow Detect Hys Lo Ref should also be adjusted by the same
amount.

45

7

70

71

72

73

74

5.10 Maintenance Parameters