Operation, 2 using the standard interface device, Rs-232 terminal communication – Alpha Technologies CFR 1500, CFR 2000, CFR 2500, CFR 3000 User Manual

Page 37: 3 remote terminal quick reference

Advertising
background image

4. OPERATION

30

4.2 Using the Standard Interface Device,

continued

Line Synchronization

When both the “LINE POWER” and “LINE FAILURE” LEDs are ON, the UPS is

synchronizing its output frequency to the utility input prior to resuming AC line
operation. Synchronization takes approximately 15 seconds. If the line frequency
(generator frequency) is out of tolerance, the UPS can not synchronize to it, and stays
in the inverter mode.

Line Failure (AC Input Out of Tolerance)

Whenever AC line voltage becomes unacceptably high or low (+10 % /

25%), or the line frequency exceeds + 3%, the "LINE PRESENT" LED
flashes and the "LINE FAILURE" LED lights indicating the UPS is
running on backup power.

NOTE: High generator THD can also cause this condition.

Line Failure Operation

Whenever a utility power outage occurs, the UPS initiates LINE FAILURE

operation without interruption of output power. The amber “LINE FAILURE” LED lights
to indicate that the UPS is running on backup power.

Fig.19

Fig. 21

Fig.22

Fig.20

Line Present Operation

The green “LINE PRESENT” LED indicates that the UPS is running on AC line

(utility / mains) power.

5. RS-232 TERMINAL COMMUNICATION

35

The menu items outlined in this manual can be accessed from a remote terminal.

The numbers contained in this guide act as a quick reference to accessing menu
functions. Single-digit numbers relate to specific main menus. Double-digit numbers
relate to specific sub-menus.

0

QUERY ALL PARAMETERS

1

SYSTEM PARAMETERS

BATTERY TEMPERATURE

11

START TEST Mode

12

STOP TEST Mode

2

INPUT PARAMETERS

VOLTAGE
CURRENT
VOLT AMPS
POWER IN WATTS
POWER FACTOR
LINE FREQUENCY

3

OUTPUT PARAMETERS

OUTPUT #1

VOLTAGE
CURRENT

OUTPUT #2

VOLTAGE
CURRENT

VOLT AMPS
POWER IN WATTS
POWER FACTOR
LINE FREQUENCY

4

BATTERY PARAMETERS

VOLTAGE
CURRENT
CHARGER STATUS
TEMPERATURE

5

USER PARAMETERS

SET TEST SCHEDULE

53

SET TEST START

55

SET TEST FREQUENCY

56

TRANSMIT UNSOLICITED ALARMS

58

SET USER SECURITY CODE

59

SET MAINTENANCE SECURITY CODE

CFR SOFTWARE VER.
MICRO BOARD SER. NO.
EEPROM VERSION NO.
POWER BOARD SER. NO.

501

START SHUTDOWN WHEN DELAY IS SET

502

START OUTPUT SHUTDOWN

503

CANCEL OUTPUT SHUTDOWN

504

RECOVER OUTPUT SHUTDOWN ONLY WHEN AC LINE RESTORED

505

SET OUTPUT SHUTDOWN DELAY

506

SET OUTPUT SHUTDOWN DURATION

507

SHUT OFF INVERTER - SAVE BATTERY

508

START UP INVERTER FROM SAVE BATTERY

509

NONE

510

TRANSMIT IPC-XXX TYPE UNSOLICITED ALARMS

511

INVERTER ON ALARM DELAY

6

- not available -

7

MAINTENANCE PARAMETERS
70

FAST DETECT LOW REF

71

FAST DETECT HIGH REF

72

MEDIUM DETECT LOW REF

73

MEDIUM DETECT HIGH REF

74

SLOW DETECT LOW REF

75

SLOW DETECT HIGH REF

76

SLOW DETECT HYS. LO REF

77

SLOW DETECT HYS. HI REF

78

MAX. PLL SLEW RATE

79

BATTERY WARNING REF.

5.3 Remote Terminal Quick Reference