Alpha Technologies Continuity: 6K_10K User Manual
Page 18
Advertising
0170012-J0 Rev A
16
Continuity 6K model
Continuity 10K model
Refer to the table below for input current, output current, and recommended conductors specifications:
• AC input and output (75°C minimum copper wire)
Model
Maximum current
Conductor section
Torque
6 kVA
33 A
AWG #8
10 kVA
54.3 A
AWG #6
23 in-lb
• Battery input
Model
Maximum current
Conductor section
6 kVA
25 A
AWG #8
10 kVA
41 A
AWG #6
Advertising