3.5.2  Start-up in Battery Mode (Cold Start)

1. Make sure the UPS has at least 1 set (20 pcs) of 12 V / 7 Ah batteries installed.

2. Press and hold the UPS On

button for approximately 5 seconds. The buzzer sounds twice. The LCD

display scrolls from Screen A to Screen G.

3. Press and hold the UPS On

button again for about 3 seconds until the LCD display scrolls from

Screen G to Screen H. The UPS is in the self-test mode and can supply power to the output after about a

minute. The LCD display will scroll to Screen I.

If a failure occurs within 15 seconds of pushing the UPS On button, the UPS will automatically switch off.

Screen G

Off means the UPS pre-start has

been successful.

Screen H1

Utility input is 0 and abnormal.

Screen H2