9400000-J0 Rev C

30

9.3 Factory Ranges and Defaults

Table D shows the rectifier settings/ranges/defaults. Changes are made through the CXC interface.

Table D —

Rectifier factory ranges and defaults

Setting

Range (minimum to maximum)

Default

Float (FL) Voltage

47.5 – 58.2 V

54 V

Equalize (EQ) Voltage

49.8 – 60.2 V

55 V

Battery Test (BT) Voltage

44 – 52 V

46 V

Over Voltage Protection (OVP)*

63 V

57 V

Current Limit (CL)

23 – 100%

100%

Power Limit (PL)

0 – 100%

100%

Module Start Delay

0 – 250 s

1 s

System Start Delay

0 – 600 s

0 s

Low Voltage Alarm (LVA)

42 – 52 V

44 V

High Voltage Alarm (HVA)

52 – 63 V

55.5 V

EQ Timeout

1 – 2399 h

30 h

BT Timeout

1 – 250 h

8 h

Softstart Ramp-rate

Normal/Fast

Normal

CL/PL Alarm

Enable/Disable

Enable

Remote Shutdown

Enable/Disable

Enable

Ramp Test

Enable/Disable

Enable

*The OVP cannot be set below the present system/FL/EQ/BT voltage setting or the safe mode voltage of 51.0 V.