41

9400004-J0 Rev B

6.3.2 Connecting the power plant frame ground

The power plant frame must also be connected to the MGB or FGB—see Figure 23. This is done for personnel

safety and to meet many telco-grounding requirements. Cable should be #6 AWG (16mm) for small to medium

size power plants and #2/0 for large plants (> 800A).

Frame ground
¼" on 5/8" centers

Figure 24 —

Frame reference ground (top of bay)

Table G — Typical Ground Reference Conductor Selection

System Ampacity

Typical ground reference conductor size

< 30A

#10

30-100A

#6-2

100-400A

0000

400-800A

350 MCM

> 800A

750 MCM