9.4 Adding Rectifier Shelves

The CAN bus provides a communication path between the controller and rectifiers. In a single bay, the CAN bus

cabling is daisy-chained from the shunt mux, if installed, to the bottom rectifier shelf. The cable is then daisy-

chained from the bottom shelf, to higher shelves, in sequence. At the last shelf, termination is enabled—see

Figure 38.

CAN termination enabled

CAN termination disabled

Figure 38 — CAN bus termination

1. Remove the left most rectifier in the top shelf of the

existing bay. (Refer to the Rectifier Shelf manual for

the removal and re-insertion procedure.)

2. Flip the DIP switches from Termination Enabled to

Termination Disabled—see Figure 38.

3. Replace the rectifier.
4. Connect the CAN bus cable to the CAN OUT

connector of the top rectifier shelf of the expansion

bay.

Figure 39 — CAN OUT connection

NOTE:

If your system has redundant rectifiers, it is recommended to power off the left most

rectifier in the top shelf of the existing bay during this procedure.