Unit Placement and Installation

THE FLOW SENSOR, PNEUMATIC TUBING AND DAMPER SHAFT ARE NOT TO BE USED FOR LIFTING OR SUPPORT.

THEY ARE CRITICAL TO THE PROPER OPERATION OF THE UNIT.

• To avoid product damage, only lift or handle the EZT by fully supporting the unit from more than one location.

• Locate unit as per construction drawings, and be careful not to conflict with articles of other trades such as plumbing

and electrical conduit.

• Consult SMACNA guidelines for proper transitioning and good workmanship practices.

• Using the support method from the construction plans and specification, suspend unit in a level horizontal plane

noting direction of airflow. When utilizing sheet metal straps, up to 1” long screws may be utilized to penetrate the
main casing. Do not secure hanging straps to unit appurtenances such as (but not limited to) electric heater cabinets,
hot water coils, and control enclosures.

For units equipped with optional hanging brackets, rods up to 3/8” diameter may be used with ANEMOSTAT
brackets. Hanger rod locations are approximately 1” to 3” from the corner of the unit for most terminal
configurations.

• Make certain not to obstruct service access to any electrical enclosures or access panels for access to the interior of

the unit.

• Check with the local Anemostat representative if a terminal must be “flipped” over from its’ intended orientation.