The modular solution for 6 kv applications, Nsg 3060 – Atec Teseq-Schaffner-NSG3060 User Manual

Page 3

Advertising
background image

A d v a n c e d Te s t S o l u t i o n s f o r E M C

Teseq AG
Nordstrasse 11F 4542 Luterbach Switzerland
T + 41 32 681 40 40 F + 41 32 681 40 48
[email protected]

www.teseq.com

THE MODULAR SOLUTION FOR 6 KV APPLICATIONS

NSG 3060

691-130B August 2009

Parameter

Value

Pulse amplitude:

±200 V to 4.8 kV (in 1 V steps) - open circuit

±100 V to 2.4 kV (50 Ω matching system)

Burst frequency:

100 Hz to 1000 kHz

Polarity:

positive / negative / alternate

Repetition time:

1 ms to 4200 s (70 min)

Burst time:

1 µs to 1999 s, single pulse, continuous

Test duration:

1 s to 1000 h

Phase synchonization:

asynchronous, synchronous 0 to 359º (in 1º steps)

Coupling:

ANSI / IEC / external

Burst (EFT) 5/50 ns
Pulse conforms to IEC/EN 61000-4-4

Dips & drops
conforms to IEC/EN 61000-4-11

Parameter

Value

Dips & drops:

From EUT voltage input to 0 V, 0%

Uvar with optional variac:

depending on model (VAR 650x)

Uvar with step transformer:

0, 40, 70, 80% (INA 650x)

Peak inrush current capability:

500 A (at 230 V)

Switching times:

1 to 5 μs (100 Ω load)

Event time:

20 µs to 1999 s, 1 to 99’999 cycles

Test duration:

1 s to 70’000 min, 1 to 99’999 events, continuous

Repetition time:

40 µs to 35 min, 1 to 99’999 cycles

Phase synchronization:

asynchronous, synchronous 0 to 359º (in 1º steps)

Variation test
conforms to IEC/EN 61000-4-11

Parameter

Value

Uvar with optional variac:

0 to 265 V (in 1 V steps), 0 to 115% (in 1% steps)

Repetition time:

1 ms to 35 min, 1 to 99’999 cycles

Test duration:

1 ms to 5 s, 1 to 250 cycles (50 Hz);

1 to 300 cycles (60 Hz), abrupt

Repetition time:

10 ms to 10 s; 1 to 250 cycles (50 Hz), 1 to 300 cycles (60 Hz)

Test duration:

1 s to 99’999 min, 1 to 99’999 events, continuous

Phase synchronization:

asynchronous, synchronous 0 to 359º (in 1º steps)

Advertising