Led f – Bray 70 Series SERVO PRO User Manual

Page 14

Advertising
background image

12

BRAY Series 70 Servo Pro

Operation and Maintenance Manual

4.4 s

tatus

led f

lasH

c

odes

Table 3 shows various diagnostic Flash Codes and

their descriptions.

If more than one advisory condition or error condition

exists, only one Flash Code will appear at a time. The

first condition must be corrected before the second (or

subsequent) Flash Code will appear.

t

able

3: s

tatus

led

flasH

codes

No.

Indication

Description

Possible Solution(s)

1

Steady Green Flash

(1 second on, 1 second

off) “Heartbeat”

Normal Operation

Servo Pro Functioning Normally

2

2 Green Flashes

Calibration Defaults

Loaded

Calibration may be acceptable, but if not, adjust

travel limits and restart the Calibration

3

3 Green Flashes

Reverse Acting Mode

Selected

This is an advisory that the Reverse Acting

mode has been selected. Adjust Configuration

switch 7 if forward operation is required.

4

4 Green Flashes

HVAC 2-10 VDC

Command Signal

Selected

This is an advisory that the HVAC 2-10 VDC

input has been selected. Adjust Configuration

switches 1, 2 and 3 if this Command Signal is

not required.

5

1 Red Flash

Handwheel engaged

Push the Handwheel in towards the actuator to

Disengage

6

2 Red Flashes

Command Signal Failure Verify Command Signal, verify wiring, adjust

Configuration switches to match Command Signal

7

3 Red Flashes

Feedback Pot Fault

Verify feedback pot wiring, position the

feedback Pot cam correctly, see Feedback Pot

calibration notes

8

4 Red Flashes

Limit Switch Fault

Verify wiring of limit switches, verify limit switch

cam settings, verify that both limit switches are

not tripped simultaneously (the actuator cannot

be fully open and fully closed at the same time)

9

5 Red Flashes

Torque Switch Fault

Verify that optional torque switches are installed

and wired correctly, reverse direction of actuator,

correct over-torque condition – OR – if optional

torque switches are not installed, disable the

torque switch input setting Configuration switch

10 to ON.

10

6 Red Flashes

Feedback Pot Wired In

Reverse

This check is only performed during Calibration.

Remove power from the Servo Pro, correct the

wiring to the feedback pot, reapply power to the

Servo Pro, and restart the Calibration.

Advertising