Bray 70 Series SERVO PRO User Manual

Page 18

Advertising
background image

16

BRAY Series 70 Servo Pro

Operation and Maintenance Manual

notice

A torque switch that is broken, improperly wired,

or missing from the actuator can result in an open

contact which will be interpreted by the Servo Pro as

the actuator being at its max torque limit.
If the optional torque switches are not installed, select

Torque Switch Disable by setting Configuration switch

10 to ON.

caution

Do not connect any high voltage power to the torque

limit switch terminals as damage could result.

5.1.7 f

eedback

P

otentiometer

The Servo Pro uses the signal from the internal

feedback potentiometer to determine the current

actuator position.

The wiring to the feedback potentiometer is connected

at the factory and should not require any adjustment

by the customer. If a field repair is required, follow the

instructions below:

5.1.7.1 f

eedback

P

otentiometer

i

nstallation

and

c

alibration

1. Install the internal feedback potentiometer next to

the actuator indicator shaft using the two threaded

mounting holes provided.

2. The potentiometer assembly must be mounted in the

correct orientation in order to successfully calibrate

the Servo Pro.

3. Remove the indicator rotor from the indicator shaft

so that the drive slot on the top is visible.

4. Engage the handwheel (pulling it fully outward)

and manually move the actuator to the fully open

(counterclockwise) position.

5. Use the black feedback pot knob to rotate the black

feedback pot cam until the raised green rib on the

pot gear (see Figure 4 below) is directly in-line with

the slot on the top of the indicator shaft.

6. The actuator is now ready for the calibration procedure

described in Section 3.1.

notice

The wiring of the feedback pot is critical to proper

operation.

Connect the orange wire from the wiper pin of the pot

to the middle terminal.

Connect the gray wire from the fixed pin of the pot that

is closest to the wiper pin to the +5V terminal.

Connect the white wire from the fixed pin of the pot

that is farthest from the wiper pin to the COM terminal.

Connect a voltmeter between the middle terminal and

the COMMON terminal. Apply power to the Servo

Pro, move the actuator to the fully open position, and

the reading should be close to +5 VDC. Move the

actuator to the fully closed position, and the reading

should be close to 0 VDC.

caution

Do not connect any high voltage power to the feedback

pot terminals as damage could result.

f

igure

4: f

eedback

P

ot

m

ounting

and

P

ositioning

.

!

!