CHILLED WATER DISTRIBUTION PIPING


The chilled water distribution piping is an important factor in the performance of the
water chiller. Proper piping will add to the LIFE of your chiller. This chiller is designed to
be a containment free system. The chilled water piping should be the same. NO BLACK
IRON PIPE.

1.

If you are installing this water chiller to some existing chiller water lines
(Black or galvanized) there is a good chance there will be rust in this
system. If you cannot flush this system clean then it should not be used. A
rust contaminated system will cause damage to the copper evaporator heat
exchanger.

2.

Should this be a new system and you are installing chilled water piping. We
suggest using PVC piping if allowed. It is a poor conductor of heat, so you
do not loose as much BTU capacity in the movement of the chilled water
and there is no rusting.

Copper line will prevent any rusting but there is greater heat loss. You
might want to insulate these li nes.

3.

Should the water chiller be installed next to your cooling load. We would
suggest rubber hose. This would prevent any great heat loss. And there
would also be no contamination.

4.

If black pipe, galvanize, iron, and steel pipe are your piping of choice, you
should be aware of the corrosiveness of these materials. Black Iron will
damage the watering system.

5.

Female connections to chiller are brass. If your connections to the chiller
are anything other than, PVC, copper, or rubber hose you should consult
with your local plumbing

supplier about the use of dielectric pipe

connections when dissimilar metals are used. If we can be of any
assistance with this please call the manufacturer.

6.

Keep in mind you should keep all chilled water lines full size. If your chiller
has 1" NPT, then the chilled water lines should be no less.