Fan motor specifications, Safety, Maintenance – Schreiber Chillers Old 4 ton MRI User Manual

Page 19

Advertising
background image




FAN MOTOR SPECIFICATIONS

Refer to your model number & voltage

Model # H.P.

Voltage

Hz R.P.M. Overload Frame Mounting Rotation

Blade

QTY.

50AC

1/4 Hp 115/208/230-1 Ph. 60

1725

Automatic

G48

Rigid O.D.P.

CW

14" x 16 Pitch

1

100AC

1/4 Hp 115/208/230-1 Ph. 60

1725

Automatic

G48

Rigid O.D.P.

CW

16" x 26 Pitch

1

100AC

1/4 Hp

460-3 Ph.

60

1140

Automatic

L48

Rigid O.D.P.

CW

16" x 26 Pitch

1

150AC

1/4 Hp 208/230/460-3 Ph. 60

1140

Automatic

L48

Rigid O.D.P.

CW

16" x 26 Pitch

1

200AC

1/2 Hp 208/230/460-3 Ph. 60

1140

Automatic

F56

Rigid O.D.P.

CW

18" x 24 Pitch

1

300AC

1/2 Hp 208/230/460-3 Ph. 60

1140

Automatic

F56

Rigid O.D.P.

CW

18" x 24 Pitch

1

400AC

1/2 Hp 208/230/460-3 Ph. 60

1140

Automatic

F56

Rigid O.D.P.

CW

18" x 24 Pitch

1

500AC

1/2 Hp 208/230/460-3 Ph. 60

1140

Automatic

F56

Rigid O.D.P.

CW

18" x 24 Pitch

1

600AC

1/2 Hp 208/230/460-3 Ph. 60

1140

Automatic

F56

Rigid O.D.P.

CW

18" x 24 Pitch

2

750AC

1/2 Hp 208/230/460-3 Ph. 60

1140

Automatic

F56

Rigid O.D.P.

CW

18" x 24 Pitch

2

800AC

1/2 Hp 208/230/460-3 Ph. 60

1140

Automatic

F56

Rigid O.D.P.

CW

18" x 24 Pitch

2

1001AC 1/2 Hp 208/230/460-3 Ph. 60

1140

Automatic

F56

Rigid O.D.P.

CW

18" x 24 Pitch

2

1000AC 1/2 Hp 208/230/460-3 Ph. 60

1140

Automatic

F56

Rigid O.D.P.

CW

18" x 24 Pitch

2

1250AC 1/2 Hp 208/230/460-3 Ph. 60

1140

Automatic

F56

Rigid O.D.P.

CW

18" x 24 Pitch

2

1500AC

1 Hp 208/230/460-3 Ph. 60

1725

Automatic

E56

Rigid O.D.P.

CW

24" x 16 Pitch

2

2000AC

1 Hp 208/230/460-3 Ph. 60

1725

Automatic

E56

Rigid O.D.P.

CW

24" x 16 Pitch

2

2500AC

1 Hp

230/460-3 Ph.

60

1725

Automatic

E56

Rigid O.D.P.

CW

24" x 16 Pitch

3

3000AC

1 Hp

460-3 Ph.

60

1725

Automatic

E56

Rigid O.D.P.

CW

24" x 16 Pitch

3

SAFETY:


Avoid personal injury or equipment damage by disconnecting electrical power before working on the motor(s).
Do not remove the door(s) while the unit is connected to electrical power.

MAINTENANCE:

1. There are no lubrication points; therefore, no lubrication is necessary
2. Make sure the blade runs in the correct direction.
3. Clean the outside of the motor as necessary.

14